3
WIRING
21
3
WIRING
WARNING
D
Only commence wiring after verifying that the power supply is turned OFF.
Failure to observe this warning can result in an electric shock or a fire.
D
Wiring should be performed only by qualified personnel.
Failure to observe this warning can result in an electric shock or a fire.
D
Make sure to ground the ground terminal
before connecting the other
terminals.
Failure to observe this warning can result in an electric shock or a fire.
D
Verify that the power regenerative unit rated voltage coincides with the AC
power supply voltage.
Failure to observe this caution can result in personal injury or a fire.
D
Do not perform a withstand voltage test of the power regenerative unit.
It may cause semi-conductor elements to be damaged.
D
Connect the power coordinating reactor and the power suppressing
reactor as described in this instruction manual.
Improper connection may cause a fire.
D
Verify that the rated voltage of the power regenerative unit coincides with
the rated voltage of the power regenerative unit to be connected.
Failure to observe this caution can result in a fire.
D
Tighten terminal screws.
Failure to observe this caution can result in a fire.
3.1
CONNECTION DIAGRAM
(1) Connection Diagram with Inverter
Fig.8 shows a diagram of a typical connection of the VS-656RC5 with the
VS-616G5.
CAUTION