3.7 Control Circuit Wiring
72
YASKAWA ELECTRIC
TOEP C710606 09B YASKAWA AC Drive V1000 Installation & Start-Up Manual
over time. Improper wiring practices could result in drive malfunction due to loose terminal connections.
◆
Control Circuit Terminal Block Functions
Drive parameters determine which functions apply to the multi-function digital inputs (S1 to
S7), multi-function digital outputs (MA, MB), multi-function pulse inputs and outputs (RP,
MP) and multi-function photocoupler outputs (P1, P2). The default is called out next to each
terminal. Refer to
WARNING!
Sudden Movement Hazard. Always check the operation and wiring of control circuits after being
wired. Operating a drive with untested control circuits could result in death or serious injury.
WARNING!
Confirm the drive I/O signals and external sequence before starting test run. Setting parameter
A1-06 may change the I/O terminal function automatically from the factory setting.
. Failure to comply may result in death or serious injury.
NOTICE:
Do not switch an input contactor more often than once every 30 minutes. Improper equipment
sequencing could shorten useful life of the drive electrolytic capacitors and circuit relays. Normally the drive
I/O should be used to stop and start the motor.
■
Input Terminals
Table 3.6 Control Circuit Input Terminals
Type
No.
Terminal Name (Function)
Function (Signal Level) Default Setting
Multi-
Function
Digital
Inputs
S1
Multi-function input 1 (Closed: Forward
run, Open: Stop)
Photocoupler
24 Vdc, 8 mA
Note:
Drive preset to sinking mode.
When using source mode, set DIP switch S3 to allow
for a 24 Vdc (
±
10%) external power supply. Refer to
S2
Multi-function input 2 (Closed: Reverse
run, Open: Stop)
S3
Multi-function input 3 (External fault
(N.O.))
S4
Multi-function input 4 (Fault reset)
S5
Multi-function input 5 (Multi-step speed
reference 1)
S6
Multi-function input 6 (Multi-step speed
reference 2)
S7
Multi-function input 7 (Jog reference)
SC
Multi-function input common (Control
common)
Sequence common
Safety
Input
HC
Power supply for safety input command
+24 Vdc (max 10 mA allowed)
H1
Safety input command
Open: Coast to stop safety input
Closed: Normal operation
Note:
Disconnect wire
jumper between HC and H1 when using safety input.