5.2
b: Application
u
b1: Operation Mode Selection
n
b1-01: Frequency Reference Source 1
Use parameter b1-01 to select the frequency reference source 1 for the REMOTE mode.
Note: 1.
If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator
LED on the digital operator will flash.
2.
Press the LO/RE key to set the drive to LOCAL and use the operator keypad to enter the frequency reference.
Setting 0: Operator keypad
Using this setting, the frequency reference can be input by:
• switching between the multi-speed references in the d1-
parameters.
• entering the frequency reference on the operator keypad.
Setting 1: Terminals (analog input terminals)
Using this setting, an analog frequency reference can be entered as a voltage or current signal from terminals A1, A2, or
A3.
Voltage Input
Voltage input can be used at any of the three analog input terminals. Make the settings as described in
for the
input used.
Table 5.5 Analog Input Settings for Frequency Reference Using Voltage Signals
Figure 5.1
Figure 5.1 Setting the Frequency Reference as a Voltage Signal at Terminal A1
Use the wiring example shown in
for any other analog input terminals. When using input A2 make sure DIP
switch S1 is set for voltage input.
Current Input
Input terminal A2 can accept a current input signal. Refer to
to set terminal A2 for current input.
Table 5.6 Analog Input Settings for Frequency Reference Using a Current Signal
No.
Parameter Name
Setting Range
Default
b1-01
Frequency Reference Source 1
0 to 4
1
Terminal
Signal Level
Parameter Settings
Notes
Signal Level Selection
Function Selection
Gain
Bias
A1
0 to 10 Vd
H3-01 = 0
H3-02 = 0
(Frequency Reference Bias)
H3-03
H3-04
-
-10 to +10 Vdc
H3-01 = 1
A2
0 to 10 Vd
H3-09 = 0
H3-10 = 0
(Frequency Reference Bias)
H3-11
H3-12
Make sure to set DIP switch S1 on the
terminal board to “V” for voltage input.
-10 to +10 Vdc
H3-09 = 1
A3
0 to 10 Vd
H3-05 = 0
H3-06 = 0
(Frequency Reference Bias)
H3-07
H3-08
Make sure to set DIP switch S4 on the
terminal board to “AI”.
-10 to +10 Vdc
H3-05 = 1
Terminal
Signal Level
Parameter Settings
Notes
Signal Level Selection
Function Selection
Gain
Bias
A2
4 to 20 mA
H3-09 = 2
H3-10 = 0
(Frequency Bias)
H3-11
H3-12
Make sure to set DIP switch S1 on the
terminal board to “I” for current input.
0 to 20 mA
H3-09 = 3
Drive
A1 Analog Input 1
0 to 10 V
AC Analog input common
2 k
Ω
+
V
-
V
10.5 V, 20 mA power supply
-
10.5 V, 20 mA power supply
A2 Analog Input 2
A3 Analog Input 3
Drive
A1 Analog Input 1
-10 to 10 V
AC Analog input common
4 k
Ω
+
V
-
V
10.5 V, 20 mA power supply
-
10.5 V, 20 mA power supply
A2 Analog Input 2
A3 Analog Input 3