Installation and Operation Guide SOLECTRIA PVI 25TL-480-R
DOCR-071030-A (11/17/2020)
Page 62 of 101
Table 5-3 Reactive Power Derating Grid Parameters
PARAMETER
NAME
SETUP RANGE
(LOWER LIMIT,
DEFAULT & UPPER
LIMIT) IEEE1547-
2018
SETUP RANGE
(LOWER LIMIT,
DEFAULT & UPPER
LIMIT) RULE21
DESCRIPTION
PFSetValue
{-1,-0.8},{1},{0.8,1} {-1,-0.8},{-0.95},{0.8,1} Local Power Factor Setting
PFpCurveP1
{0%,50%,100%}
{0%,50%,100%}
Power of PF(P)Curve point 1
PF_PCurvePF1
{-1,-0.8},{1},{0.8,1} {-1,-0.8},{1},{0.8,1}
PF of PF(P)Curve point 1
PFpCurveP2
{0%,100%,100%}
{0%,100%,100%}
Power of PF(P)Curve point 2
PF_PCurvePF2
{-1,-0.8},{-
0.9},{0.8,1}
{-1,-0.8},{-0.9},{0.8,1} PF of PF(P)Curve point 2
PFpCurveTriVolt
{100%,100%,110%} {100%,100%,110%}
The trigger voltage of PF(P)Curve
PFpCurveUndoVolt {90%,90%,100%}
{90%,90%,100%}
The end voltage of PF(P)Curve
QuCurveU1
{100%,102%,110%} {100%,103.3%,110%} Voltage of Q(U)Curve point 1
QuCurveQ1
{-60%,0%,60%}
{-60%,0%,60%}
Reactive power of Q(U)Curve point 1
QuCurveU2
{100%,108%,110%} {100%,107%,110%}
Voltage of Q(U)Curve point 2
QuCurveQ2
{-60%,-44%,60%}
{-60%,-30%,60%}
Reactive power of Q(U)Curve point 2
QuCurveU1i
{90%,98%,99%}
{90%,96.7%,99%}
Voltage of Q(U)Curve point 1i
QuCurveQ1i
{-60%,0%,60%}
{-60%,0%,60%}
Reactive power of Q(U)Curve point
1i
QuCurveU2i
{80%,92%,100%}
{80%,92%,100%}
Voltage of Q(U)Curve point 2i
QuCurveQ2i
{-60%,44%,60%}
{-60%,30%,60%}
Reactive power of Q(U)Curve point
2i
QuCurveTriPower
{5%,20%,100%}
{5%,20%,100%}
The trigger power of Q(U)Curve
QuCurveUndoPower {5%,5%,100%}
{5%,5%,100%}
The end power of Q(U)Curve
LVRT/HVRT
5.2.2.2.4
The “LVRT/HVRT” submenu is used to set the LVRT (Low Voltage Ride-Through) and HVRT (High Voltage Ride-Through)
parameters as shown in Figure 5-13: