Installation and Operation Guide SOLECTRIA PVI 25TL-480-R
DOCR-071030-A (11/17/2020)
Page 49 of 101
connect it to the access point created by the FOMlink dongle. Choose the Wi-Fi Network named “CPLK-
XXXXXXX”, where XXXXXX is the serial number (SN) found on the side of the FOMlink Dongle Module.
4.
The inverter will need to be initialized on the first start up.
a.
Figure 4-2 System Setting
Grid Standard:
Select a grid standard
Figure 4-3 Grid Standard Options
INFO
✔
Selection of Grid Standard:
Please check with your local electric utility company before selecting a grid standard. If the
inverter is operated with a wrong grid standard, the electricity supply company may cancel the interconnection
agreement.
Placing the inverter into operation before the overall system complies with the national rules and safety regulations of
the application is not permitted.
b.
PV Link Type
: The DC input configuration and MPP Tracker shall only be configured as Independent.
c.
Neutral Line Setting
: Enter whether a neutral line is installed or not.
d.
RS485
: Enter the communication data Modbus Address and Baud Rate.