YASKAWA SI-P3V Technical Manual Download Page 18

18

YASKAWA ELECTRIC

 SIEP C730600 23B V1000 Option PROFIBUS-DP Technical Manual

7  Conventional Formats

7

Conventional Formats

‹

Conventional Formats

The configuration tool of PROFIBUS-DP master sets the input and output data length of SI-P3/V from Extended Data 1 
(32 bytes), Extended Data 2 (12 bytes), and Basic Data (6 bytes).

Conventional formats have two message types: High-speed I/O Data and MEMOBUS/Modbus message.

Set parameter F6-32 to “1” to use conventional formats.

„

High-Speed I/O Data

High-speed I/O data is directly transferred to or from the drive and can control the drive. For example, when the drive is 
set for PROFIBUS-DP communications, the drive Run/Stop and Frequency Reference commands are typically 
transferred to the drive within 2 ms after being received by the option.

„

MEMOBUS/Modbus Message

MEMOBUS/Modbus message data is transferred to the drive using MEMOBUS/Modbus messages. All drive parameters 
and data can be accessed through MEMOBUS/Modbus. Because the data in this message type is transferred to the drive 
after the SI-P3/V receives and edits it, more time is required to return the data to the master. The master must synchronize 
the timing of sending and receiving the data by handshaking.

„

Memory Maps

The following memory maps show the I/O data bytes. 

„

Basic and Extended Register Maps

Table 9  Basic Data Register Map Detail

Table 10  Extended Data 1 Register Map

Basic Data 

(6 bytes)

Extended Data 1 

(32 bytes)

Extended Data 2 

(12 bytes)

High-speed I/O Data

Bytes 0 to 5

Bytes 0 to 15

Bytes 0 to 3

MEMOBUS/Modbus Data

Bytes 16 to 31

Bytes 4 to 11

Output (Master Device to Drive)

Input (Drive to Master Device)

Byte

<1> Unit depends on the setting of o1-03 (Digital Operator Display Scaling). When the drive is operating in the V/f Control mode, the drive's output 

frequency becomes the input data.

<2> Data is displayed in units of either 0.01 A for drives 7.5 kW and smaller, or in units of 0.1 A for drives 11 kW and larger. This is the same 

regardless of whether the drive is set for Normal Duty or Heavy Duty operation.

Description

Byte

Description

0

Operation Command (High Byte) 

0

Drive Status (High Byte)

1

Operation Command (Low Byte)

1

Drive Status (Low Byte)

2

Frequency Reference (High Byte)

2

Motor Speed (High Byte)

<1>

3

Frequency Reference (Low Byte)

3

Motor Speed (Low Byte)

<1>

4

Reserved

4

Output Current (High Byte)

<2>

5

5

Output Current (Low Byte)

<2>

Output (Master Device to Drive)

Input (Drive to Master Device)

Byte

Description

Byte

Description

0

Operation Command (High Byte)

0

Drive Status (High Byte)

1

Operation Command (Low Byte)

1

Drive Status (Low Byte)

2

Frequency Reference (High Byte)

2

Motor Speed (High Byte)

<3>

3

Frequency Reference (Low Byte)

3

Motor Speed (Low Byte)

<3>

Summary of Contents for SI-P3V

Page 1: ...Technical Manual PROFIBUS DP Type SI P3 V YASKAWA AC Drive V1000 Option To properly use the product read this manual thoroughly and retain for easy reference inspection and maintenance Ensure the end...

Page 2: ...This Page Intentionally Blank...

Page 3: ...ed stored in a retrieval system or transmitted in any form or by any means mechanical electronic photocopying recording or otherwise without the prior written permission of Yaskawa No patent liability...

Page 4: ...f its products Applicable Documentation The following manuals are available for the PROFIBUS DP Option Terms Note Indicates a supplement or precaution that does not cause drive damage Registered Trade...

Page 5: ...ording to the instructions described in this manual Any illustrations photographs or examples used in this manual are provided as examples only and may not apply to all products to which this manual i...

Page 6: ...re de l alimentation pour permettre la decharge des condensateurs Pour repondre aux exigences s assurer que le neutre soit relie a la terre pour la serie 400V WARNING Read manual before installing Wai...

Page 7: ...tion connects a drive to a field network using the PROFIBUS DP protocol PROFIBUS DP is included into the European Fieldbus Standard EN 50170 The network is primarily used in process and factory automa...

Page 8: ...see Figure 2 If you receive the wrong model or the PROFIBUS DP Option does not function properly contact your supplier Contents and Packaging Table 2 Contents of Package Tool Requirements Note Tools...

Page 9: ...pin D sub connector for installing the option card Once installed the drive can connect to a PROFIBUS network A LED Comm green 1 Cables are not connected to the PROFIBUS DP Option and are packaged sep...

Page 10: ...3 V and drive are not connected properly and or there is no power supplied to the SI P3 V An internal self diagnostic error occurred in the SI P3 V ERR Option Error Red ON SI P3 V error Self diagnosti...

Page 11: ...P3 V Self diagnostics error The PROFIBUS DP Option is damaged Cycle power to the drive If the LED status does not change replace the PROFIBUS DP Option Problem connecting to the drive Problem initiali...

Page 12: ...used according to the instructions described in this manual Do not allow unqualified personnel to use equipment Failure to comply could result in death or serious injury Maintenance inspection and rep...

Page 13: ...es below 1 5 Mbps 1 5 Mbps and higher baud rates require termination with resistors as shown in Figure 7 Figure 5 Figure 6 PROFIBUS Cable Connection with Termination Resistors Properly connect all pin...

Page 14: ...result in death or serious injury Before installing the PROFIBUS DP Option disconnect all power to the drive The internal capacitor remains charged even after the power supply is turned off The charg...

Page 15: ...ct the PROFIBUS DP Option to the drive Properly secure the tabs on the left and right sides of the PROFIBUS DP Option to the drive case Figure 11 Figure 12 Attach PROFIBUS DP Option 6 Connect the grou...

Page 16: ...e at http www profibus com Cable Requirements Table 6 Communication Cable Requirements Cable Length Communication speed determines maximum permissible cable length Table 7 shows the specifications for...

Page 17: ...lects the run command input source 0 Digital Operator RUN and STOP keys 1 Digital input terminals S1 to S7 6 2 MEMOBUS Modbus communications 3 Option PCB 1 F6 01 Operation Selection after Communicatio...

Page 18: ...ing memory maps show the I O data bytes Basic and Extended Register Maps Table 9 Basic Data Register Map Detail Table 10 Extended Data 1 Register Map Basic Data 6 bytes Extended Data 1 32 bytes Extend...

Page 19: ...Modbus Data 3 Low Byte 26 MEMOBUS Modbus Data 4 High Byte 26 MEMOBUS Modbus Data 4 High Byte 27 MEMOBUS Modbus Data 4 Low Byte 27 MEMOBUS Modbus Data 4 Low Byte 28 Reserved 28 Reserved 29 29 30 30 31...

Page 20: ...cription 0 1 During run 1 1 During zero speed 2 1 During reverse run 3 1 During fault reset signal input 4 1 During speed agree 5 1 Drive ready 6 1 Alarm 7 1 Fault 8 1 During operation error oPE 9 1 D...

Page 21: ...Starting resistor No High Byte 18 Low Byte 19 Number of Data Items Sets the number of bytes to read or write only 2 4 6 or 8 allowed 20 Data 1 1 Data word 1 High Byte 21 Low Byte 22 Data 2 1 Data wor...

Page 22: ...Hz 0 01 Hz 3000 BB8H Example 2 5 is assigned as the bias for terminal FM of multi function analog output 1 5 0 1 50 32H Converted into a two complement FFCEH Example 3 60 00 Hz is assigned for d1 01...

Page 23: ...haking Input Register SI P3 V Unit to PROFIBUS DP Master Bit 7 6 5 4 3 2 1 0 HS INIT Bit Name Function 7 HS Handshaking bit Synchronizes send and receive timing Changes status when sending new command...

Page 24: ...Figure 14 Figure 15 Example of Handshaking 0 0 1 1 1 1 0 0 0 0 1 0 0 0 0 1 1 1 1 0 0 0 PROFIBUS DP Master Handshaking Output Register etc SI P3 V Unit Handshaking Input Register Command Executed Resp...

Page 25: ...sage Creates a command message Sends to slave Toggles handshaking register HS bit 1 INDATA HS Handles the response START Clears handshaking register HS bit to 0 Receives for the master Command message...

Page 26: ...rs PKE PPO type 1 8 octets PKW 4 octets PZD PPO type 2 8 octets PKW 12 octets PZD PPO type 3 4 octets PZD PPO type 4 12 octets PZD PPO type 5 8 octets PKW 20 octets PZD Bit PPO Write PPO Read 0 PNU nu...

Page 27: ...ue for d1 17 in drives running software version 2102 and later The software version appears on the drive nameplate indicated by PRG OFF1 reserved Ready to switch on always 1 1 OFF2 reserved Ready alwa...

Page 28: ...sfer number of array element 7 Task cannot be executed with error number Parameter Setting Value Note GSD_Revision 3 GSD file revision 3 0 Vendor_Name YASKAWA ELECTRIC Model_Name PROFIBUS DP INTERFACE...

Page 29: ...en 240 C2_Response_Timeout 100 C2_Read_Write_required 0 C2_Max_Count_Channels 1 Max_Initiate_PDU_Length 52 Modular_Station 1 Modular station Max_Module 1 Maximum of modules 1 Max_Input_Len 32 Maximum...

Page 30: ...904 Unsigned 16 Current PPO Write 905 Octet String 28 Type 5 PPO Write 907 Octet String 12 Type 1 PPO Read 908 Octet String 20 Type 2 PPO Read 909 Octet String 4 Type 3 PPO Read DP V1only 910 Octet St...

Page 31: ...5th Word data of PPO type 1 PWE STW STW data ZSW Up to drive status HIW Up to drive status Data type Settings Description PKE 638BH 6 Request parameter value from Array 38BH 907 dec PNU 907 IND 5 5th...

Page 32: ...PPO Write 2 Type 2 PPO Write 3 Type 3 PPO Write 4 Type 4 PPO Write 5 Type 5 PPO Write ZSW Up to drive status HIW Up to drive status PZD PNU INDX Assigned PNU Description PZD1 915 1 P0 1 Operation com...

Page 33: ...p 00 99 22 b2 Function Group 00 99 23 b3 Function Group 00 99 24 b4 Function Group 00 99 25 b5 Function Group 00 99 26 b6 Function Group 00 99 28 b8 Function Group 00 99 31 C1 Function Group 00 99 32...

Page 34: ...153 o3 Function Group 00 99 154 o4 Function Group 00 99 171 q1 Function Group 00 99 181 r1 Function Group 00 99 201 T1 Function Group 00 99 211 U1 Function Group 00 99 212 U2 Function Group 00 99 213...

Page 35: ...us 45 0 002EH MEMOBUS Modbus 46 0 002FH MEMOBUS Modbus 47 0 0030H MEMOBUS Modbus 48 0 0031H MEMOBUS Modbus 49 0 0032H MEMOBUS Modbus 50 0 0033H MEMOBUS Modbus 51 0 0034H MEMOBUS Modbus 52 0 xxx xxx 0...

Page 36: ...17 PWE 258H d1 17 value STW Up to drive status HSW Up to drive status Data type Settings Description PKE 212CH 2 Change parameter setting value 12CH 300 IND 0 N A PWE 0 N A STW Up to Master command HS...

Page 37: ...b1 02 3 Cause Possible Solution Master controller PLC has stopped communicating Check for faulty wiring Correct any wiring problems Communication cable is not connected properly A data error occurred...

Page 38: ...ID error Cause Possible Solution PROFIBUS DP Option hardware fault Replace the PROFIBUS DP Option Contact Yaskawa for assistance LED Operator Display Minor Fault Name bb Baseblock Data format and sett...

Page 39: ...nications Speed 9 6 kbps to 12 Mbps Ambient Temperature 10 C to 50 C Humidity Up to 95 RH no condensation Storage Temperature 20 C to 60 C allowed for short term transport of the product Area of Use I...

Page 40: ...085 U S A Phone 1 847 887 7000 Fax 1 847 887 7370 YASKAWA ELETRICO DO BRASIL LTDA Avenida Fagundes Filho 620 Sao Paulo SP CEP 04304 000 Brazil Phone 55 11 3585 1100 Fax 55 11 5581 8795 YASKAWA ELECTRI...

Reviews: