background image

10 General Class Objects

82

YASKAWA

SIEP C730600 84G DeviceNet Technical Manual

Instance ID

Attribute

Name

Description

Get

Set

Size

Range

Default

156

3

Data

Same function as the Enhanced
Control Status (Input Assembly)

-

Array 8 Bytes

-

00 00 00 00 00
00 00 00

157

3

Data

Same function as the Standard DI/
DO Status (Input Assembly)

-

Array 8 Bytes

-

00 00 00 00 00
00 00 00

158

3

Data

Same function as the Standard Status
4 (Input Assembly)

-

Array 8 Bytes

-

00 00 00 00 00
00 00 00

159

*2

3

Data

Same function as the Dynamic Input
Assembly (Input Assembly)

-

Array 8 Bytes

-

00 00 00 00 00
00 00 00

199

*1

3

Data

Same function as the Change of
State Response (Input Assembly)

-

Array 8 Bytes

-

00 00 00 00 00
00 00 00

*1

The drive is compatible with option software versions 1107 and later.

*2

The drive is compatible with option software versions 1111 and later.

DeviceNet Connection Object - 5 (Class 0x05)

Services Supported

Service Code No. (Hex)

Service Name

0E

Get Attribute Single

10

Set Attribute Single

Attributes Supported

Instance ID

Attribute

Name

Description

Get

Set

Size

Range

Default

0

1

Object Software Revision

DeviceNet Connection object software
revision

-

Word

-

1

1

Explicit

1

State

Status of the instance.

00: Network not found or not yet
connected.

01: Online, awaiting connection from
the master.

02: Waiting to write the connection
ID.

03: Connected successfully.

04: Timeout.

-

Byte

-

3

2

Instance type

Shows the instance type.

00: Explicit message

01: I/O message

-

Byte

-

0

3

Transport class trigger

Defines behavior of the connection.

-

Byte

-

83 (Hex.)

4

Produced connection ID

The label used in the comm. header
for the drive.

Set once the comm. connection is
complete.

-

Word

-

-

5

Consumed connection ID

-

Word

-

-

6

Initial comm characteristics

Code for the comm. type.

-

Byte

-

21 (Hex.)

7

Produced connection size

Maximum number of bytes that can be
transmitted.

-

Byte

-

-

8

Consumed connection size

Maximum number of bytes received.

-

Byte

-

-

9

Expected packet rate

The time to timeout after receiving a
comm. request. Rounds up to the
nearest 10 ms.

Word

0 - 65535

2500

12

Watchdog time-out action

Action taken after timeout.

00: Save value until reset or power is
shut off

01: Auto delete

02: Restart while remaining connected

-

Byte

-

1

13

Produced connection path
length

Number of bytes for the transmission
connection path.

-

Word

-

0

14

Produced connection path

Specifies the application object that
will produce data by this Connection
Object.

-

Array

-

-

15

Consumed connection path
length

Number of bytes in the consumed
connection path.

-

Word

-

0

16

Consumed connection path

Specifies the Application Object that
will receive data consumed by this
Connection Object.

-

Array

-

-

Summary of Contents for SI-N3/V

Page 1: ...YASKAWA AC Drive Option DeviceNet Technical Manual Model SI N3 To correctly use the product read this manual thoroughly and keep it for easy reference inspection and maintenance Make sure that the end...

Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEP C730600 84G DeviceNet Technical Manual...

Page 3: ...ock CN1 11 Option LED States 11 Power Up Diagnostics 12 5 Installation Procedure 12 Section Safety 12 Procedures to Install and Wire Options on a Drive 13 Procedure A 13 Procedure B 16 Procedure C 19...

Page 4: ...ric YE Assy 121 0x79 47 Speed Command 2 Vendor Specific Yaskawa Electric YE Assy 122 0x7A 48 Torque Command 2 Vendor Specific Yaskawa Electric YE Assy 123 0x7B 48 Speed Dynamic Assy Vendor Specific Ya...

Page 5: ...Services Supported 79 Attributes Supported 80 DeviceNet Object 3 Class 0x03 80 Services Supported 80 Attributes Supported 80 Assembly Object 4 Class 0x04 80 Services Supported 80 Attributes Supported...

Page 6: ...atic Device Replacement ADR 95 Configuration Recovery CR 95 Auto Address Recovery AAR 95 13 Trunk Line and Drop Line Length 95 Trunk Line 95 Drop Line 96 14 European Standards 96 EMC Directive Complia...

Page 7: ...his book The technical manual contains detailed information about the option Access the following sites to obtain the technical manual U S http www yaskawa com Europe http www yaskawa eu com Japan htt...

Page 8: ...ion circuitry Failure to obey can cause serious injury or death or cause damage to the drive or option and will void warranty Yaskawa is not responsible for modifications of the product made by the us...

Page 9: ...of option manuals by product and a direct link to download a PDF of the manual Scan QR code Or refer to http www yaskawa com optionlookup Install the Option on a GA500 Drive An option card mounting ki...

Page 10: ...1000 Series Z1000U 1 GA500 GA700 and GA800 1 Manuals 1 1 GA700 and GA800 drives do not use the ground wire 2 Only two screws are necessary to install the option on GA700 and GA800 drives Note The LED...

Page 11: ...ion Table 4 1 Terminal Descriptions Terminal Pin Color Signal Description 1 Black V Network common 2 Blue CAN_L CAN data Low 3 Shield Cable shield 4 White CAN_H CAN data High 5 Red V Communications ne...

Page 12: ...nications faulted state The device then received and accepted an Identify communication fault request long protocol message Power Up Diagnostics An LED test is performed each time the drive is powered...

Page 13: ...ion incorrectly NOTICE Damage to Equipment Correctly connect the connectors Incorrect connections can cause malfunction or damage to the equipment NOTICE Damage to Equipment Make sure that all connect...

Page 14: ...after the drive is de energized The charge indicator LED extinguishes when the DC bus voltage decreases below 50 Vdc When all indicators are OFF measure for dangerous voltages to make sure that the d...

Page 15: ...the drive and use the included screws B to put it in place A Option B Included screw C Connector CN5 A Figure 5 4 Install the Option 4 Use one of the remaining included screws B to connect one end of...

Page 16: ...t When you touch the option make sure that you observe correct electrostatic discharge ESD procedures If you do not follow procedures it can cause ESD damage to the drive circuitry 6 Reattach the fron...

Page 17: ...rgized drive Before servicing disconnect all power to the equipment and wait for the time specified on the warning label at a minimum The internal capacitor stays charged after the drive is de energiz...

Page 18: ...he temporary placement holes B on the right side of the drive Refer to the drive manuals for more information NOTICE Do not remove the LED Status Ring board cable connector If you disconnect the LED S...

Page 19: ...nd keypad D Refer to the drive manuals for more information NOTICE Do not pinch cables between the front cover or the LED Status Ring board and the drive Failure to comply could cause erroneous operat...

Page 20: ...wait for the time specified on the warning label at a minimum The internal capacitor stays charged after the drive is de energized The charge indicator LED extinguishes when the DC bus voltage decreas...

Page 21: ...e the Front Cover and Keypad 2 Put the LED label B in the correct position on the drive front cover A A Drive front cover B LED label Figure 5 15 Put the LED Label on the Drive Front Cover Note On FP6...

Page 22: ...ounding terminal A A Drive grounding terminal FE B Included screw Figure 5 17 Remove the Screw from the Drive Grounding Terminal 4 Use the screw B installed in the FE ground terminal of the drive A to...

Page 23: ...n A into the CN5 A connector C on the drive and use one of the included screws B to put it in place Tighten the screw to a correct tightening torque 0 5 N m to 0 6 N m 4 4 in lb to 5 3 in lb Note 1 On...

Page 24: ...ceNet communication cable to the option terminal block CN1 Isolate communication cables from main circuit wiring and other electrical and power lines Make sure that you firmly connect the cable end Re...

Page 25: ...am 1 Connect the included ground wire for installations on 1000 series GA500 and FP605 drives The ground wire is not necessary for installations on GA700 or GA800 drives Communication Cable Wiring Rou...

Page 26: ...drive Incorrect connections can also cause death or serious injury from fire NOTICE Do not let wire shields touch other signal lines or equipment Insulate the wire shields with electrical tape or shr...

Page 27: ...U S http www yaskawa com Europe http www yaskawa eu com Japan http www e mechatronics com Other areas Check the back cover of these manuals For questions contact Yaskawa or a Yaskawa representative N...

Page 28: ...0 3 F6 06 03A7 Torque Reference Limit by Comm Sets the function that enables and disables the torque reference and torque limit received from the communication option 0 Disabled 1 Enabled Note Control...

Page 29: ...ing and F6 53 DeviceNet PPA Setting are not correct the value is reset to default 21 0 255 F6 53 03C4 DeviceNet PPA Setting Sets the format of data that the drive sends to the DeviceNet communication...

Page 30: ...MOBUS register Note The drive is compatible with option software versions 1111 and later 0 0 FFFF F6 69 03E4 Dynamic In Assembly 159 Param 2 Sets Configurable Input 2 read from the MEMOBUS register No...

Page 31: ...endor Specific Yaskawa Electric YE Assy PCA 8 102 66 Accel Decel Time Vendor Specific Yaskawa Electric YE Assy PCA 8 103 67 1 3 Wire Control 1 Vendor Specific Yaskawa Electric YE Assy PCA 4 104 68 1 3...

Page 32: ...r Setting Connection Path Types The option can set the produced connection path and the consumed connection path with supported application tools Class 5 Instance 2 Attributes 100 101 allow setting co...

Page 33: ...rom network 0 Depends on b1 01 1 Enables the speed reference from network Speed Reference Speed Reference Sets drive speed reference Speed reference data Frequency reference 2SS SS Speed scale Setting...

Page 34: ...ue Limit High Byte Name Description Run Fwd Forward Run Command 0 Stop 1 Forward Run Run Rev Reverse Run Command 0 Stop 1 Reverse Run Fault Reset Fault Reset 0 1 Fault Reset NetCtrl Run command is fro...

Page 35: ...t 4 Multi Function Input 3 Run Rev Run Fwd 1 1000 Series GA500 Multi Function Photocoupler 2 GA700 GA800 FP605 Multi Function Digital Output 3 1000 Series GA500 Multi Function Photocoupler 1 GA700 GA8...

Page 36: ...P2 1 0 P2 OFF 1 P2 ON This function is enabled only when H2 04 F Speed Reference Speed Reference Sets drive speed reference Units are determined by parameter o1 03 Frequency Display Unit Selection Un...

Page 37: ...05 ON Multi Function Input 6 Terminal S6 Function Input 0 Terminal S6 Function H1 06 OFF 1 Terminal S6 Function H1 06 ON Multi Function Input 7 Terminal S7 Function Input 0 Terminal S7 Function H1 07...

Page 38: ...for 1000 Series GA500 GA800 or FP605 drives 3 Wire Control1 Vendor Specific Yaskawa Electric YE Assy 103 0x67 Note The drive is compatible with option software versions 1107 and later Output Instance...

Page 39: ...pler 1 GA700 GA800 FP605 Multi Function Digital Output 2 1000 Series GA500 Multi Function Digital Output GA700 GA800 FP605 Multi Function Digital Output 1 Function Code High Bit Function Code Low Bit...

Page 40: ...GA700 GA800 Terminal P1 1 0 P1 OFF 1 P1 ON FP605 0 MD MF OFF 1 MD MF ON This function is enabled only when H2 03 F Multi Function Digital Output 4 2 Terminal P2 1 0 P2 OFF 1 P2 ON This function is ena...

Page 41: ...OFF 1 Terminal S3 Function H1 03 ON Multi Function Input 4 Terminal S4 Function Input 0 Terminal S4 Function H1 04 OFF 1 Terminal S4 Function H1 04 ON Multi Function Input 5 Terminal S5 Function Inpu...

Page 42: ...Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 107 0 Multi Function Input 8 Multi Function Input 7 Multi Function Input 6 Multi Function Input 5 Multi Function Input 4 Multi Function Input 3 Ru...

Page 43: ...i Function Digital Output 4 2 Terminal P2 1 0 P2 OFF 1 P2 ON This function is enabled only when H2 04 F Analog Output 1 Analog Output FM This function is enabled only when H4 01 000 Terminal FM Analog...

Page 44: ...rminal S7 Function H1 07 ON Multi Function Input 8 Terminal S8 Function Input 0 Terminal S8 Function H1 08 OFF 1 Terminal S8 Function H1 08 ON External Fault External Fault EF0 0 1 External Fault EF0...

Page 45: ...eters that are used Note The drive is compatible with option software versions 1111 and later Output Instance Byte Description 109 0 Configurable Output 1 Low Byte 1 Configurable Output 1 High Byte 2...

Page 46: ...or Specific Yaskawa Electric YE Assy 120 0x78 Output Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 120 0 Multi Function Input 8 Multi Function Input 7 Multi Function Input 6 Multi Func...

Page 47: ...Run Run Rev Reverse Run Command 0 Stop 1 Reverse Run Multi Function Input 3 Terminal S3 Function Input 0 Terminal S3 Function H1 03 OFF 1 Terminal S3 Function H1 03 ON Multi Function Input 4 Terminal...

Page 48: ...t 6 Terminal S6 Function Input 0 Terminal S6 Function H1 06 OFF 1 Terminal S6 Function H1 06 ON Multi Function Input 7 Terminal S7 Function Input 0 Terminal S7 Function H1 07 OFF 1 Terminal S7 Functio...

Page 49: ...Input 0 Terminal S8 Function H1 08 OFF 1 Terminal S8 Function H1 08 ON External Fault External Fault EF0 0 1 External Fault EF0 Fault Reset Fault Reset 0 1 Fault Reset Torque Reference Torque Limit T...

Page 50: ...Terminal S7 Function H1 07 ON Multi Function Input 8 Terminal S8 Function Input 0 Terminal S8 Function H1 08 OFF 1 Terminal S8 Function H1 08 ON Service Code Service Code Refer to Table 8 5 for inform...

Page 51: ...unction H1 08 OFF 1 Terminal S8 Function H1 08 ON Service Code Service Code Refer to Table 8 5 for information Class Class Valid Classes are Control Supervisor Object 41 and AC DC Object 42 Instance w...

Page 52: ...isplay Unit Selection Unit is not affected by Speed Scale SS Torque Reference Torque Limit Torque Reference Torque Limit Sets the Torque Reference Torque Limit Sets in units of 0 1 Sets the Torque Ref...

Page 53: ...received by this node An Input Assembly is outputted from this node and read by the PLC This section details Input Assemblies that are Produced by this drive Basic Speed Control Input 70 0x46 Input I...

Page 54: ...or Reverse Running 1 Forward Running Running 2 REV Reverse Running 0 Stop or Forward Running 1 Reverse Running Ready Drive Ready 0 Not Ready 1 Ready Ctrl from Net Run command is from network 0 Run co...

Page 55: ...ows the Torque Reference Value displays in 0 1 units Extended Speed and Torque Control Input 73 0x49 Input Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 73 0 At Speed Ref from Net Ctrl...

Page 56: ...ve is compatible with option software versions 1107 and later Input Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 104 0 Fault Actual Direction Direction Command Running Ready 1 Referen...

Page 57: ...t A2 1 0 0 0 From Network Bytes 2 3 1 0 0 1 1 0 1 0 1 0 1 1 1 1 0 0 1 1 0 1 1 1 1 0 1 1 1 1 Speed Status Vendor Specific Yaskawa Electric YE Assy 130 0x82 Input Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 B...

Page 58: ...hotocoupler 2 GA700 GA800 FP605 Multi Function Digital Output 3 1000 Series GA500 Terminal P2 1 0 P2 OFF 1 P2 ON GA700 GA800 Terminal P1 1 0 P1 OFF 1 P1 ON FP605 0 MD MF OFF 1 MD MF ON Multi Function...

Page 59: ...o Alarm 1 Alarm Fault Drive Fault 0 No Fault 1 During Fault Uv Undervoltage 0 1 Undervoltage LOCAL REMOTE Run command is from network 0 Run command is not from network 1 Run command is from network 10...

Page 60: ...605 Multi Function Digital Output 3 1000 Series GA500 Multi Function Photocoupler 1 GA700 GA800 FP605 Multi Function Digital Output 2 1000 Series GA500 Multi Function Digital Output GA700 GA800 FP605...

Page 61: ...rent Unit 0 1A Unit is not affected by Current Scale CS Output Frequency Actual Drive Speed Monitors drive output frequency Units are determined by parameter o1 03 Frequency Display Unit Selection Uni...

Page 62: ...not affected by Speed Scale SS Note This is a paired assembly 124 134 Table 9 3 Reply Mapping 134 Byte Write Success Read Success Write Failure Read Failure Busy Illegal Function Code Function Code E...

Page 63: ...Unit is not affected by Current Scale CS Note This is a paired assembly 125 135 Table 9 4 Reply Mapping 135 Byte Write Success Read Success Write Failure Read Failure Busy Illegal Function Code Functi...

Page 64: ...t Drive Fault 0 No Fault 1 During Fault Uv Undervoltage 0 1 Undervoltage LOCAL REMOTE Run command is from network 0 Run command is not from network 1 Run command is from network 1000 Series GA500 Mult...

Page 65: ...Read Success Write Failure Read Failure Invalid Function Code Function Code Equals Zero 0 0x10 0x03 0x90 0x83 Function Code Or ed with 0x80 0 1 Output Assembly Register Number High Byte Output Assemb...

Page 66: ...tput 3 1000 Series GA500 Multi Function Photocoupler 1 GA700 GA800 FP605 Multi Function Digital Output 2 1000 Series GA500 Multi Function Digital Output GA700 GA800 FP605 Multi Function Digital Output...

Page 67: ...tput Torque Shows the Torque Reference Value displays in 0 1 units Actual Current Actual Output Current Monitors drive output current Unit 0 1A Unit is not affected by Current Scale CS 1 Terminals are...

Page 68: ...0 GA800 FP605 Multi Function Digital Output 1 1000 Series GA700 GA800 FP605 Terminal M1 M2 0 M1 M2 OFF 1 M1 M2 ON GA500 Terminal MA MB 0 MA MB OFF 1 MA MB ON 1000 Series GA500 Multi Function Photocoup...

Page 69: ...eed Agree Reset REV Running ZSP Running 1 1000 Series GA500 Multi Function Photocoupler 2 GA700 GA800 FP605 Multi Function Digital Output 3 1000 Series GA500 Multi Function Photocoupler 1 GA700 GA800...

Page 70: ...frequency Units are determined by parameter o1 03 Frequency Display Unit Selection Unit is not affected by Speed Scale SS Register Number MEMOBUS Modbus Register Number Register Data MEMOBUS Modbus R...

Page 71: ...4 5 6 Actual Current Low Byte 7 Actual Current High Byte Name Description Running Running 0 Stop 1 Forward or Reverse Running ZSP Zero Speed 0 Running 1 Stop or DC Injection Braking REV Running Rever...

Page 72: ...more information 2 Multi function digital output 4 is not available for 1000 Series GA500 GA800 or FP605 drives Note Refer to the MEMOBUS Modbus Data Table in the drive Technical Manual for a list of...

Page 73: ...2 ON Multi Function Input 3 Terminal S3 0 Terminal S3 OFF 1 Terminal S3 ON Multi Function Input 4 Terminal S4 0 Terminal S4 OFF 1 Terminal S4 ON Multi Function Input 5 Terminal S5 0 Terminal S5 OFF 1...

Page 74: ...Torque Status Dynamic Vendor Specific Yaskawa Electric YE Assy 158 0x9E Input Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 158 0 Fault Alarm Ready Speed Agree Reset REV Running ZSP Ru...

Page 75: ...Function Digital Output 4 2 Terminal P2 1 0 P2 OFF 1 P2 ON Actual Torque Output Torque Shows the Torque Reference Value displays in 0 1 units Register Number MEMOBUS Modbus Register Number Register Da...

Page 76: ...1 and later Input Instance Byte Description 159 0 Configurable Input 1 Low Byte 1 Configurable Input 1 High Byte 2 Configurable Input 2 Low Byte 3 Configurable Input 2 High Byte 4 Configurable Input 3...

Page 77: ...Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 199 0 Multi Function Input 4 Multi Function Input 3 NetCtrl NetRef Fault Reset External Fault Run Rev Run Fwd 1 Multi Function Input 8 Multi Function In...

Page 78: ...0 Terminal S7 Function H1 07 OFF 1 Terminal S7 Function H1 07 ON Multi Function Input 8 Terminal S8 command by Network 0 Terminal S8 Function H1 08 OFF 1 Terminal S8 Function H1 08 ON Running Running...

Page 79: ...ord 44 1 2 Device Type The device profile The profile for this product is an AC drive 2 AC drive Word 2 1 3 Product Code Product codes determined by the manufacturer Word 1 1 4 Revision Software revis...

Page 80: ...itch Changed since last Power up Bool 0 1 7 Baud Rate Switch Changed Indication that Baud Rate Switch Changed since last Power up Bool 0 1 8 MAC ID Switch Value The MAC ID setting value Setting throug...

Page 81: ...bly Array 8 Bytes 00 00 00 00 00 00 00 00 120 3 Data Same function as the Speed Command 1 Output Assembly Array 4 Bytes 00 00 00 00 121 3 Data Same function as the Torque Command 1 Output Assembly Arr...

Page 82: ...ork not found or not yet connected 01 Online awaiting connection from the master 02 Waiting to write the connection ID 03 Connected successfully 04 Timeout Byte 3 2 Instance type Shows the instance ty...

Page 83: ...path length Number of bytes for the transmission connection path Word 2 6 14 Produced connection path Specifies the application object that will produce data by this Connection Object Array 2 20 Hex 0...

Page 84: ...th a bUS Option Communication Error Motor Data Object 40 Class 0x28 Services Supported Service Code No hex Service Name 0E Get Attribute Single 10 Set Attribute Single Attributes Supported Instance ID...

Page 85: ...Loop Vector PM Closed Loop Vector E1 05 Maximum Output Voltage is used When A1 02 8 EZ Vector Control E9 05 Base Voltage is used Control Supervisor Object 41 Class 0x29 Services Supported Service Cod...

Page 86: ...trol Power Undervoltage 4 3222 Uv3 Soft Charge Answerback Fault 6 2120 GF Ground Fault 7 2300 oC Overcurrent 8 3210 ov Overvoltage 9 4200 oH Heatsink Overheat 10 4210 oH1 Heatsink Overheat 11 2220 oL1...

Page 87: ...rives 52 8000 dv3 Inversion Detection Note This fault is not displayed on GA500 or FP605 drives 53 8000 dv4 Inversion Prevention Detection Note This fault is not displayed on GA500 or FP605 drives 54...

Page 88: ...l Note When using GA500 GA700 or GA800 drives the following setting value 0 is added 0 Advanced OLV for PM Read only 0 EZOLV Read only When using an FP605 drive the following setting value 0 is added...

Page 89: ...s for torque related data Byte 15 15 0 1 26 Power Scale 15 to 15 Setting for F6 59 DeviceNet Power Scaling scale of units for power related data Byte 15 15 0 1 27 Voltage Scale 15 to 15 Setting for F6...

Page 90: ...Not Settable 2 Attempting to access an invalid parameter results in a DeviceNet error code of 0x09 Invalid Attribute Value 3 Refer to Explicit Message Communications Errors on page 92 for error codes...

Page 91: ...unications cable wiring is incorrect Check for wiring errors Correct the wiring An existing short circuit or communications disconnection Check disconnected cables and short circuits and repair as nee...

Page 92: ...a service code of 94 and an error code from the following table as the data Table 12 1 Explicit Message Error Codes Causes and Possible Solutions Error Code Description Cause Possible Solutions 08FF S...

Page 93: ...andL6 06 Torque Detection Time 2 settings Check system mechanics 0F 7110 rr Dynamic Braking Transistor Fault Cycle drive power If the fault stays replace the drive 10 7112 rH Braking Resistor Overheat...

Page 94: ...oss bUS 1000 Power on DeviceNet network is off Connection Time out bUS 1001 This nodes timer Expect Packet Rate timed out Dup MAC ID bUS 1002 This node and at least one other node have the same MAC ID...

Page 95: ...it will use this value to determine if a download will occur If the CCV in the scanner does not equal the CCV in the DeviceNet node the configuration information saved in the scanner will be download...

Page 96: ...It is required for engaging in business and commerce in Europe This option displays the CE mark based on the EMC Directive EMC Directive 2014 30 EU Drives used in combination with this option and dev...

Page 97: ...to the metal panel according to Figure 14 2 Figure 14 3 and Figure 14 4 Figure 14 2 Option Installation for CE Compliance 1000 Series GA700 GA800 Figure 14 3 Option Installation for CE Compliance GA50...

Page 98: ...on Equipment Comply with the EMC Directive to conform to the Korean Radio Act 16 Specifications Specifications Table 16 1 Option Specifications Items Specifications Model SI N3 Supported Messages Grou...

Page 99: ...ive materials or flammable materials including wood Dangerous gases or fluids Salt Direct sunlight Falling objects Altitude Up to 1000 m 3281 ft 17 Disposal Disposal Instructions Correctly dispose of...

Page 100: ...adio Waves Act March 2022 5 All Addition Information on FP605 Revision Reviewed and corrected entire documentation March 2019 4 All Addition Applicable product series Revision Reviewed and corrected e...

Page 101: ...YASKAWA SIEP C730600 84G DeviceNet Technical Manual 101...

Page 102: ...a Piraporinha Diadema S o Paulo 09950 000 Brasil Phone 55 11 3585 1100 Fax 55 11 3585 1187 www yaskawa com br YASKAWA EUROPE GmbH Hauptstra e 185 65760 Eschborn Germany Phone 49 6196 569 300 Fax 49 61...

Reviews: