8 Object Dictionary
32
YASKAWA ELECTRIC
SIEP C730600 64A 1000-Series Option SI-ES3 Technical Manual
2010 (Hex) - Speed Reference/Speed Limit
Sets the speed reference or speed limit. The unit of this value depends on the setting of the drive parameter o1-03.
The value will be used as the speed reference for speed control (d5-01 = 0) or as the speed limit in torque control (d5-01
= 1).
Note:
The availability of the torque control function depends on the drive and the selected control mode. For details, refer to the
technical manual for the drive.
2020 (Hex) - Torque Reference/Torque Limit
This object sets the torque reference or the torque limit in units of 0.1%.
To use this object, set drive parameter F6-06 to 1. The value will be used as the torque reference for torque control (d5-01
= 1) or as the torque limit in speed control (d5-01 = 0).
Note:
The availability of the torque control and torque limit function depends on the drive and the selected control mode. For details,
refer to the technical manual for the drive.
2030 (Hex) - Torque Compensation
This object sets the torque compensation in units of 0.1%.
2040 (Hex) - MEMOBUS/Modbus Read Request
This object can be used to read out the content of drive MEMOBUS/Modbus registers. The address of the MEMOBUS/
Modbus must be written in byte 3 and 4 of Subindex 1, and bytes 1 and 2 must be set to 0. After sending a MEMOBUS/
Modbus Read Request to the drive, the MEMOBUS/Modbus register content can be read out from object 2140H.
5
Terminal S2 Function
Multi-Function Input: H1-02
6
Terminal S3 Function
Multi-Function Input: H1-03
7
Terminal S4 Function
Multi-Function Input: H1-04
8
Terminal S5 Function
Multi-Function Input: H1-05
9
Terminal S6 Function
Multi-Function Input: H1-06
A
Terminal S7 Function
Multi-Function Input: H1-07
B
Terminal S8 Function
Multi-Function Input: H1-08
C to F
Not used
–
Index (Hex)
Subindex
Content
Access
PDO Mapping
Data Length
2010
0
Speed reference/Speed limit
Read/Write
Possible
2 byte
1
Value
Read/Write
Rx/Tx
–
Speed reference/Speed limit
The unit of this value depends on the setting of the drive parameter o1-03.
o1-03:
0: Hz
1: % (100% = E1-04)
2: rev/min (enter the number of motor poles into E2-04/E4-04/E5-04)
3: User defined by parameters o1-10 and o1-11
2
MEMOBUS/Modbus register address
Read Only
No
–
Value (MEMOBUS/Modbus register): 0x0002 (Frequency reference)
Index (Hex)
Subindex
Content
Access
PDO Mapping
Data Length
2020
0
Torque reference/Torque limit
Read/Write
Possible
2 byte
1
Value
Read/Write
Rx/Tx
–
2
MEMOBUS/Modbus register address
Read Only
No
–
Value (MEMOBUS/Modbus register): 0x0004 (Torque ref/limit)
Index (Hex)
Subindex
Content
Access
PDO Mapping
Data Length
2030
0
Torque compensation
Read/Write
Possible
2 byte
1
Value
Read/Write
Rx/Tx
–
2
MEMOBUS/Modbus register address
Read Only
No
–
Value (MEMOBUS/Modbus register): 0x0005 (Torque compensation)
Bit No. (Hex)
Description
Function