8 Communication
40
YASKAWA ELECTRIC
SIEP C730600 89C YASKAWA AC Drive Option SI-EP3 Technical Manual
PROFIdrive Profile-Specific Parameters
PROFIdrive parameters contain data of the drive in standard form. The table below describes the supported PROFIdrive
parameters.
Fault Buffer Mechanism
PROFIdrive profile has a mechanism that can store five fault situations to PROFIdrive parameters. Fault and diagnostic
data, like fault number and fault code can be accessed simultaneously with only one subindex. The mechanism consists
of two PROFIdrive parameters:
• PNU944: Fault message counter
• PNU947: Fault numbers according to value in U2-01
Parameter
R/W
Data type
Description
922 R Unsigned16
Telegram
selection
944
R
Unsigned16
Fault message counter
947 R
Array
[5]
Unsigned16
Fault number. (coded according to DRIVECOM profile) Subindex Contents, see
parameter 945.
964 R
Array
[6]
Unsigned16
Device identification Subindex Contents 0 Manufacturer 1 Device type 2 Version 3
Firmware date (year) 4 Firmware date (day/month) 5 Number of Drive Objects (DO)
965
R
Octet String2
Profile number of this device. 0328h = Profile 3, Version 40
967 R Unsigned16
Control
word
(CW)
968
R
Unsigned16
Status word (SW)
972 R/W Unsigned16
Software reset Value Description 0 No action 1 Power-cycle PROFINET IO module
The parameter must do a zero-to-one transition and the motor must be stopped.
977 R/W Unsigned16
Stores parameters to non-volatile memory Value Description 0 No action 1 Stores
parameters The parameter must do a zero-to-one transition and the motor must be
stopped.
61000 R VisibleString24
Name
of
station
61001
R
Unsigned32
IP of station
61002
R
Array [6] Unsigned8
MAC of station
61003 R Unsigned32
Default
gateway of station
61004
R
Unsigned32
Subnet mask of station