Supported motors
Permanent magnet, Synchronous AC
rotary or linear motor
Max. output frequency range
Must be lower than 500 [rev/sec].
Note: UL application: 400 [rev/sec] (200
V), 300 [rev/sec] (400 V).
If UL is needed, the combination should be
applied to UL on customer side.
Supported scales for motor driving usage
A quad B
Supported scales for fully-closed usage
A quad B
Motor pole informa-
tion for motor driving
Without hall sensor
signals
Sigma-5 detecting function is available.
In other cases, the function should be car-
ried out each boot-up.
With hall sensor sig-
nals
The data is used (any functions needed for
the information).
Unsupported option modules
INDEXER option module: SGDV-OCA03A
MP2600iec option module: SGDV-
OCC02A
Advanced safety option module: SGDV-
OSA01A
Fully-closed option module: SGDV-
OFA01A
4.3 SERVOPACK Installation Environment and Harmonized Standards
SERVOPACK installation environment and harmonized standards are as follows.
Chap. 4.2.1 ‘General Specifications’ page 30
n
Mounting in a Control Panel
To prevent the temperature around the SERVOPACK from exceeding 55 °C, take into
account the size of the control panel, the layout of the SERVOPACK, and the cooling
method. For details, refer to chapter
SERVOPACK Installation
in the manual of the
SERVOPACK.
n
Mounting Near a Heating Unit
To prevent the temperature around the SERVOPACK from exceeding 55 °C, sup-
press radiant heat from the heating unit and temperature rise due to convection.
n
Mounting Near a Vibration Source
To prevent vibration from being transmitted to the SERVOPACK, install a vibration
isolator underneath the SERVOPACK.
n
Mounting to a Location Exposed to Corrosive Gas
Take measures to prevent exposure to corrosive gas. Corrosive gases will not imme-
diately affect the SERVOPACK, but will eventually cause electronic components and
contactor-related devices to malfunction.
n
Other Locations
Do not mount the SERVOPACK in locations subject to high temperatures, high
humidity, dripping water, cutting oil, dust, iron filings, or radiation.
Installation Environment
Installation Precautions
Sigma-5 and Sigma-7 Series SERVOPACKs
Specifications
SERVOPACK Installation Environment and Harmonized Standards
| | Feedback Option Module Type 3 - Manual version C - Revision 0 | en |