10 SERVOPACK with Semi-closed Loop Control for Rotary Motors
10-2
10.1
Magnetic Pole
For driving third party motors and some Sigma-1 motors, the magnetic pole should be coordinated. The
parameters in the following table are used for that.
Parameter Setting
Note 1. If the relation between origin and U phase position is not sure, please set Pn081.2 to 1. Otherwise motor malfunc-
tion may occur.
2. In case the hall sensor is not available refer to chapter 10-4.
Parameter
Function
Default Value
When enabled
No.
Dig.
Pn080
Application Function Select Switch 80
-
-
0
Hall Sensor Selection
0
After restart
0
Enables hall sensor
1
Disables hall sensor
Pn081
Application Function Select Switch 81
-
-
2
Coordination Setting between Origin and U-phase position
0
After restart
0
Both positions are same
1
The positions are different
3
Hall Sensor Signal Inversion
0
After restart
0
Does not inverse the signals (Pos-Logic)
1
Inverses the signals (Neg-Logic)
Positive logic
Pn080.0 = 0
Pn081.2 = 0
Pn081.3 = 0
Pn080.0 = 0
Pn081.2 = 0
Pn081.3 = 1
Pn080.0 = 0
Pn081.2 = 1
Pn081.3 = 0
Pn080.0 = 0
Pn081.2 = 1
Pn081.3 = 1
Pn080.0 = 1
Pn081.2 = 0
Pn081.3 = 0
Negative logic
Positive logic
Same position
Available
Not available
Different Position
Negative logic
Hall Sensor
Origin and U-phase
Hall Sensor Signal
Parameter Setting