3.4.1 Technical data
Order no.
307-1EA00
Type
PS 307
SPEED-Bus
-
Technical data power supply
Input voltage (rated value)
AC 120/230 V
Input voltage (permitted range)
AC 90...132/180...264 V
Mains frequency (rated value)
50...60 Hz
Mains frequency (permitted range)
47...63 Hz
Input current (at 120 V)
2.2 A
Input current (at 230 V)
1.3 A
Inrush current (at 25 °C)
45 A
I²t
1.2 A²s
Power consumption typ.
138 W
Output voltage (rated value)
24 V
Output current (rated value)
5 A
Power supply parallel switchable
-
Protect type
short circuits (electr.) non-latching, overload, vacancy
Ripple of output voltage (max.), BW=20 MHz
150 mV
Efficiency typ.
87 %
Power loss typ.
18 W
Status information, alarms, diagnostics
Status display
yes
Interrupts
no
Process alarm
no
Diagnostic interrupt
no
Diagnostic functions
no
Diagnostics information read-out
none
Supply voltage display
none
Group error display
none
Channel error display
none
Housing
Material
PPE
Mounting
Rail System 300
Mechanical data
Dimensions (WxHxD)
80 mm x 125 mm x 120 mm
Net weight
610 g
VIPA System 300
Power supply PS 307
PS 307-1EA00 > Technical data
HB130 | PS | 307-1xA00 | en | 18-01