YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
139
1.7 H: Terminal Functions
Pa
ra
m
et
er D
et
ai
ls
1
1.7
H: Terminal Functions
H parameters are used to assign functions to the external terminals.
◆
H1: Multi-Function Digital Inputs
■
H1-01 to H1-06: Functions for Terminals S1 to S6
These parameters assign functions to the multi-function digital inputs. The settings 0 to 9F
determine function for each terminal and are explained below.
Note:
If not using an input terminal or if using the through-mode, set that terminal to “F”.
Table 1.40 Digital Multi-Function Input Settings
No.
<1> Number appearing in parenthesis is the default value after performing a 3-wire initialization.
Parameter Name
Setting
Range
Default
H1-01 Digital Input S1 Function Selection 1 to 9F 40: Forward Run Command (2-wire sequence)
H1-02 Digital Input S2 Function Selection 1 to 9F 41: Reverse Run Command (2-wire sequence)
H1-03 Digital Input S3 Function Selection 0 to 9F 24: External Fault
H1-04 Digital Input S4 Function Selection 0 to 9F 14: Fault Reset
H1-05 Digital Input S5 Function Selection 0 to 9F 3 (0)
: Multi-Step Speed Reference 1
H1-06 Digital Input S6 Function Selection 0 to 9F 4 (3)
: Multi-Step Speed Reference 2
Setting
Function
Page
Setting
Function
Page
0
3-Wire Sequence
PID Integral Hold
1
LOCAL/REMOTE Selection
Multi-Step Speed Reference 4
2
External Reference 1/2
34
PID Soft Starter Cancel
3
Multi-Step Speed Reference 1
35
PID Input Level Selection
4
Multi-Step Speed Reference 2
40
Forward Run/Stop (2-wire sequence)
5
Multi-Step Speed Reference 3
41
Reverse Run/Stop (2-wire sequence)
6
Jog Reference Selection
42
Run/Stop (2-wire sequence 2)
7
Accel/Decel Time 1
43
FWD/REV (2-wire sequence 2)
8
Baseblock Command (N.O.)
44
Offset Frequency 1 Addition
9
Baseblock Command (N.C.)
45
Offset Frequency 2 Addition
A
Accel/Decel Ramp Hold
46
Offset Frequency 3 Addition
B
Drive Overheat Alarm (OH2)
60
DC Injection Braking Command
C
Terminal A2 Enable
61
External Speed Search Command 1
F
Not used (through mode)
62
External Speed Search Command 2
Summary of Contents for OYMC V1000
Page 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Page 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Page 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...