5.7 H: Terminal Functions
5.7
H: Terminal Functions
H parameters are used to assign functions to the external terminals.
u
H1: Multi-Function Digital Inputs
n
H1-03 to H1-07: Functions for Terminals S3 to S7
These parameters assign functions to the multi-function digital inputs. The various functions and their settings are listed
in
.
Table 5.6 Multi-Function Digital Input Terminal Settings
Setting 3 to 5: Multi-Step Speed Reference 1 to 3
Switches multi-step speed frequency references d1-01 to d1-08 by digital inputs. Refer to
for details.
Setting 7: Accel/decel ramp selection 1
Switches between accel/decel times 1 (C1-01 and C1-02) and 2 (C1-03 and C1-04). Refer to
Decel Ramps 1 to 4 on page 109
for details.
Setting 8, 9: Baseblock command (N.O., N.C.)
When the drive receives a baseblock command, the output transistors stop switching, the motor coasts to stop, and a bb
alarm flashes on the digital operator to indicate baseblock.
WARNING! Sudden Movement Hazard. When using a mechanical holding brake with the drive in a lifting application, close the brake
when the drive output is cut off by a baseblock command triggered by one of the input terminals. Failure to comply will result in a
slipping load from the motor suddenly coasting when the baseblock command is entered and may cause serious injury or death.
Setting F: Not used (Through mode)
Select this setting when using the terminal in a pass-through mode. When set to F, an input does not trigger any function
in the drive. Setting F, however, still allows the input status to be read out.
No.
Parameter Name
Setting Range
Default
H1-03
Terminal S3 Function Selection
3 to 79
50: Nominal Speed
H1-04
Terminal S4 Function Selection
3 to 79
51: Intermediate Speed
H1-05
Terminal S5 Function Selection
3 to 79
52: Releveling Speed
H1-06
Terminal S6 Function Selection
3 to 79
53: Leveling Speed
H1-07
Terminal S7 Function Selection
3 to 79
F: Not Used
Setting
Function
Page
Setting
Function
Page
3
Multi-Step Speed Reference 1
20 to 2F
External Fault
4
Multi-Step Speed Reference 2
40
Forward Run/Stop
5
Multi-Step Speed Reference 3
41
Reverse Run/Stop
7
Accel/decel Ramp Selection 1
50
Nominal Speed
8
Baseblock Command (N.O.)
51
Intermediate Speed
9
Baseblock Command (N.C.)
52
Releveling Speed
F
Not used (Through Mode)
53
Leveling Speed
14
Fault Reset
54
Inspection Operation
15
Emergency Stop (N.O.)
55
Rescue Operation
17
Emergency Stop (N.C.)
56
Motor Contactor Feedback
18
Timer Function Input
79
Brake Feedback
1A
Accel/decel Ramp Selection 2
-
-
DIgital Input Function
Drive Operation
Input Open
Input Closed
Setting 8 (N.C.)
Baseblock (Interrupt output)
Normal operation
Setting 9 (N.O.)
Normal operation
Baseblock (Interrupt output)
Summary of Contents for Lift Inverter L1000V
Page 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...