4.6 Setup Procedure for Elevator Applications
86
YASKAWA EUROPE SIEP
YASKAWA AC Drive L1000V Technical Manual
u
Speed Selection Using Digital Inputs (b1-01 = 0)
Set parameter b1-01 = 0 to enable the speed selection using the drive digital inputs. Use parameter d1-18 to determine
different travel speeds selected by the digital inputs.
n
Multi-Speed Inputs 1, 2 (d1-18 = 0 or 3)
Speed Selection
When d1-18 = 0 or 3, multi-function digital inputs are preset as shown below.
Different speed reference settings can be selected by combining the three digital inputs as shown in the table below.
Note:
Parameters d1-19 through d1-26 are displayed only if d1-18 is set to 1 or 2.
Setting d1-18 = 0
Up to eight speed references can be set using parameters d1-01 to d1-08. The drive starts with an Up or Down command,
and stops when the Up or Down command is removed. When d1-18 = 0, parameters d1-19 through d1-23 will not be
displayed.
Setting d1-18 = 3
Allows seven speed references to be set using parameters d1-02 to d1-08. The drive starts with an Up or Down
command, and stops either when all three input terminals that set the speed reference are released, or when the Up/Down
command is released. When d1-18 = 0, parameters d1-19 through d1-23 will not be displayed.
n
Separate Speed Inputs (d1-18 = 1 or 2)
Six different speed settings (defined in the parameters d1-19 to d1-24 and d1-26) can be set and selected using four
digital inputs.
Speed Selection
When d1-18 = 1 or 2, multi-function digital inputs are preset as shown below:
d1-18
Speed Selection
0 (default)
Multi-speed inputs 1, Speed references are set in d1-01 to d1-08
1
Separate speed inputs, Speed references are set in d1-19 to d1-24 and d1-26, Higher speed has priority
2
Separate speed inputs, Speed references are set in d1-19 to d1-24 and d1-26, Leveling speed has priority
3
Multi speed inputs 2, Speed references are set in d1-02 to d1-08, Stop if no speed selection input is enabled
Terminal
Parameter Number
Set Value
Details
S5
H1-05
3
Multi-Speed Reference 1
S6
H1-06
4
Multi-Speed Reference 2
S7
H1-07
5
Multi-Speed Reference 3
Digital Inputs
0 = Off, 1 = On
Selected Speed
Multi-Speed
Reference 1
Multi-Speed
Reference 2
Multi-Speed
Reference 3
d1-18 = 0
d1-18 = 3
0
0
0
Speed reference 1 (d1-01)
Stop
1
0
0
Speed reference 2 (d1-02)
0
1
0
Speed reference 3 (d1-03)
1
1
0
Speed reference 4 (d1-04)
0
0
1
Speed reference 5 (d1-05)
1
0
1
Speed reference 6 (d1-06)
0
1
1
Speed reference 7 (d1-07)
1
1
1
Speed reference 8 (d1-08)
Terminal
Parameter Number
Set Value
Details
S3
H1-03
50
Nominal speed (d1-19)
S4
H1-04
54
Inspection speed (d1-24)
S5
H1-05
51
Intermediate speed (d1-20)
S6
H1-06
53
Leveling speed (d1-26)
Summary of Contents for Lift Inverter L1000V
Page 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Page 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...