CAUTION!
Since the power section supply is not internally protected, it is to be exter-
nally protected with a fuse, which corresponds to the maximum current.
This means max. 10A is to be protected by a 10A fuse (fast) respectively
by a line circuit breaker 10A characteristics Z!
n
The power section supply is to be externally protected with a fuse, which corresponds
to the maximum current. This means max. 10A is to be protected with a 10A fuse
(fast) respectively by a line circuit breaker 10A characteristics Z!
n
It is recommended to externally protect the electronic power section supply for CPU
an I/O area with a 2A fuse (fast) respectively by a line circuit breaker 2A characteris-
tics Z.
After PowerON the RUN respectively MF LED at every System SLIO module is on, so far
as the sum current does not exceed the maximum value. With the CPU this is 3A. If the
total current exceeds the maximum value, the LEDs are no longer triggered. Here the
power module with the order number 007-1AB10 is to be placed between the periphery
modules.
2.5.2.2
Wiring 8x periphery modules
CAUTION!
Do not connect hazardous voltages!
If this is not explicitly stated in the corresponding module description,
hazardous voltages are not allowed to be connected to the corresponding
terminal module!
With wiring the terminal modules, terminals with spring clamp technology are used for
wiring. The spring clamp technology allows quick and easy connection of your signal and
supply lines. In contrast to screw terminal connections this type of connection is vibration
proof.
U
max
240V AC / 30V DC
I
max
10A
Cross section
0.08 ... 1.5mm
2
(AWG 28 ... 16)
Stripping length 10mm
Fusing
State of the electronic
power supply via LEDs
Terminal module terminals
Data
iC9200 Series
Basics and mounting
Wiring > Wiring System SLIO periphery