9.4 A: Initialization Parameters
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
595
9.4
A: Initialization Parameters
◆
A1: Initialization
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
A1-00
(0100)
RUN
Language Selection
Sets the language for the HOA keypad.
Note:
When you use
A1-03 [Initialize Parameters]
to initialize the drive, the drive will not
reset this parameter.
0 : English
5 : Spanish
0
(0, 5)
A1-01
(0101)
RUN
Access Level Selection
Sets user access to parameters. The access level controls which parameters the keypad will
display and which parameters you can set.
0 : Operation Only
1 : User Parameters
2 : Advanced Level
3 : Expert Level
4 : Lock Parameters
2
(0 - 4)
A1-03
(0103)
Initialize Parameters
Sets parameters to default values.
0 : No Initialization
1110 : User Initialization
2220 : 2-Wire Initialization
0
(0, 1110, 2220)
A1-04
(0104)
Password
Entry point for the password set in
A1-05 [Password Setting]
. The user can view the
settings of parameters that are locked without entering the password. Enter the correct
password in this parameter to change parameter settings.
0000
(0000 - 9999)
A1-05
(0105)
Password Setting
Sets a password to lock parameters and prevent changes to parameter settings. Enter the
correct password in
A1-04 [Password]
to unlock parameters and accept changes.
0000
(0000 - 9999)
A1-06
(0127)
Application Preset
Sets the drive to operate in selected application conditions.
0 : No Preset Selected
1 : General Purpose Fan
2 : Fan w/ PID Control
3 : Return Fan w/ PID Control
4 : Cooling Tower Fan
5 : Cooling Tower Fan w/ PID
6 : Secondary Pump
7 : Pump w/ PID Control
0
(0 - 7)
A1-11
(111D)
Expert
Firmware Update Lock
Protects the drive firmware. When you enable the protection, you cannot update the drive
firmware.
0 : Disabled
1 : Enabled
0
(0, 1)
A1-12
(1564)
Bluetooth ID
Sets the password necessary to use Bluetooth to control the drive with a smartphone or
tablet.
-
(0000 - 9999)
◆
A2: User Parameters
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
A2-01
(0106)
User Parameter 1
Sets the parameter number to be shown for number 1 of the [User Custom Parameters]
under the main menu. You can select a maximum of 32 parameters for the drive and set
them to parameters
A2-01
to
A2-32
.
A1-02
(A1-00 - Z3-16)
A2-02
(0107)
User Parameter 2
Sets the parameter number to be shown for number 2 of the [User Custom Parameters]
under the main menu. You can select a maximum of 32 parameters for the drive and set
them to parameters
A2-01
to
A2-32
.
b1-01
(A1-00 - Z3-16)
A2-03
(0108)
User Parameter 3
Sets the parameter number to be shown for number 3 of the [User Custom Parameters]
under the main menu. You can select a maximum of 32 parameters for the drive and set
them to parameters
A2-01
to
A2-32
.
b1-02
(A1-00 - Z3-16)
A2-04
(0109)
User Parameter 4
Sets the parameter number to be shown for number 4 of the [User Custom Parameters]
under the main menu. You can select a maximum of 32 parameters for the drive and set
them to parameters
A2-01
to
A2-32
.
b1-03
(A1-00 - Z3-16)
A2-05
(010A)
User Parameter 5
Sets the parameter number to be shown for number 5 of the [User Custom Parameters]
under the main menu. You can select a maximum of 32 parameters for the drive and set
them to parameters
A2-01
to
A2-32
.
C1-01
(A1-00 - Z3-16)
Summary of Contents for HV600
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...