84
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Model
H6BP
Standard Non-Fused
Input Disconnect Switch S1
With Option PM
Circuit Breaker CB1
Current Rating
Amps
AWG, kcmil
Tightening Torque
(in lb)
Current Rating
Amps
AWG, kcmil
Tightening Torque
(in lb)
D088
150
14 - 10 or 8 - 3/0
50 or 120
150
14 - 10 or 8 - 3/0
50 or 120
D114
175
4 - 4/0
225
150
14 - 10 or 8 - 3/0
50 or 120
D143
250
3/0-350 kcmil
225
250
3/0 - 350 kcmil
225
D169
250
3/0-350 kcmil
225
250
3/0 - 350 kcmil
225
D211
400
(1-2) x (2/0-500 kcmil)
(1-2) x 442
400
(1-2) x (2/0-500 kcmil)
(1-2) x 442
D273
400
(1-2) x (2/0-500 kcmil)
(1-2) x 442
600
(1-2) x (2/0-500 kcmil)
(1-2) x 442
Table 3.6 Output and Control Wiring
Model
H6BP
Motor Wiring
Standard Motor
Terminal Block TB1
Ground Wiring
Control Wiring
AWG,
kcmil
Tightening
Torque
(in lb)
AWG,
kcmil
Tightening
Torque
(in lb)
A1
Terminal Blocks
TB1, TB3-TB6
A1
Terminal Block
TB2 (FE)
A2
Terminal Blocks
TB1-TB4 and TB6
Panel
Terminal Block
TB4
AWG,
kcmil
Tightening
Torque
(in lb)
AWG,
kcmil
Tightening
Torque
(in lb)
AWG,
kcmil
Tightening
Torque
(in lb)
AWG,
kcmil
Tightening
Torque
(in lb)
D002
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
D003
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
D004
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
D007
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
D010
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
D016
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
D024
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
D030
14-2
32
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
D046
14-2
32
14-10, 8, 6-
4, or 2-1/0
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
D059
14-2
32
14-10, 8, 6-
4, or 2-1/0
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
D074
6-2/0
120
14-10, 8, 6-
4, or 2-1/0
35, 40, 45,
or 50
24-16
4.4 to 5.3
24-18
8.85 to
10.62
26-14
4
26-10
5.3 to 7.1
D088
14 - 8 or 6 -
2/0
50 or 120
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24 - 16
4.4 to 5.3
24-18
8.85 to
10.62
26 - 14
4
26-10
5.3 to 7.1
D114
14 - 10 or 8
or 6 - 2/0
35 or 40 or
120
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24 - 16
4.4 to 5.3
24-18
8.85 to
10.62
26 - 14
4
26-10
5.3 to 7.1
D143
6 - 350
kcmil
275
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24 - 16
4.4 to 5.3
24-18
8.85 to
10.62
26 - 14
4
26-10
5.3 to 7.1
D169
6 - 350
kcmil
275
14-10, 8, 6-
4, or 2
35, 40, 45,
or 50
24 - 16
4.4 to 5.3
24-18
8.85 to
10.62
26 - 14
4
26-10
5.3 to 7.1
D211
(1-2) x (4 -
500 kcmil)
(1-2) x 500
14 - 2/0
120
24 - 16
4.4 to 5.3
24-18
8.85 to
10.62
26 - 14
4
26-10
5.3 to 7.1
D273
(1-2) x (4 -
500 kcmil)
(1-2) x 500
14 - 2/0
120
24 - 16
4.4 to 5.3
24-18
8.85 to
10.62
26 - 14
4
26-10
5.3 to 7.1
*1
24-16 is acceptable for solid wire or ferrule use only.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...