YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
543
7.9
Drive Derating
You must derate the drive capacity to operate the drive above the rated temperature, altitude, and default carrier
frequency.
◆
Carrier Frequency Settings and Rated Current Values
, and
show how the drive rated output current changes when the
C6-02 [Carrier
Frequency Selection]
value changes. The output current value changes linearly as the carrier frequency changes. You
can use the values from the tables to calculate a frequency that is not shown.
Note:
The drive will apply derating for the rated output current value based on the carrier frequency only to the reference output current value of
the
oL2 [Drive Overload]
. The derated value for the 100% rated output current in parameters and monitors will not be the same as the rated
output current value shown in the Model Specifications tables.
■
208 V Models
Table 7.22 Carrier Frequency and Rated Current Derating
Bypass Model
Drive Model
Rated Current (A)
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
D002 to D010
2011
10.6
10.6
8.9
7.8
6.4
D016
2017
16.7
16.7
14.0
12.2
10.0
D024
2024
24.2
24.2
20.3
17.7
14.5
D030
2031
30.8
30.8
25.9
22.6
18.5
D046
2046
46.2
46.2
38.8
33.9
27.7
D059
2059
59.4
59.4
49.9
43.6
35.6
D074
2075
74.8
74.8
62.8
54.9
44.9
D088
2088
88.0
88.0
73.9
64.5
52.8
D114
2114
114
114
95.8
83.6
68.4
D143
2143
143
143
114.4
95.3
-
D169
2169
169
169
135.2
112.7
-
D211
2211
211
211
168.8
140.7
-
D273
2273
273
273
218.4
182
-
■
240 V Models
Table 7.23 Carrier Frequency and Rated Current Derating
Bypass Model
Drive Model
Rated Current (A)
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
A002 to A009
2011
10.6
10.6
8.9
7.8
6.4
A015
2017
16.7
16.7
14.0
12.2
10.0
A022
2024
24.2
24.2
20.3
17.7
14.5
A028
2031
30.8
30.8
25.9
22.6
18.5
A042
2046
46.2
46.2
38.8
33.9
27.7
A054
2059
59.4
59.4
49.9
43.6
35.6
A068
2075
74.8
74.8
62.8
54.9
44.9
A080
2088
88.0
88.0
73.9
64.5
52.8
A104
2114
114
114
95.8
83.6
68.4
A130
2143
143
143
114.4
95.3
-
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...