YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
419
■
Y4-42: Output Disconnect Detection Sel
No.
(Hex.)
Name
Description
Default
(Range)
Y4-42
(3D23)
Output Disconnect Detection
Sel
This parameter applies only when in Drive Mode. It sets the drive response if the connection between
the drive and the motor is disconnected.
0
(0 - 3)
Note:
1. Loss Of Load
[Z1-31 to Z1-36]
, Load Verify
[Z1-53]
, and Bypass Energy Savings
[Z1-16]
can interfere with the correct operation of
Output Disconnect Detection.
2. When the Output Disconnect is active, the drive internally disables Output Phase Loss Detection of more than one phase.
0 : Disabled
1 : Alarm - Speed Search
The drive will show an
OD [Output Disconnect]
alarm. When you close the output again, the drive will do a
baseblock and a Speed Search for the correct recovery.
Note:
If at any time the customer Run command is removed, the drive will clear the
OD
alarm and enter a normal stopped state.
2 : Alarm - Start at Zero
The drive will show an
OD
alarm. When you close the output again, the drive will do a baseblock and let the soft-
starter to ramp up from zero for the correct recovery.
Note:
If at any time the customer Run command is removed, the drive will clear the
OD
alarm and enter a normal stopped state.
3 : Fault
The drive will coast to stop and show an
OD [Output Disconnect]
fault.
Note:
You cannot Auto-Restart the drive after an
OD
fault.
■
Y4-43: Output Disconnect Inject Current
No.
(Hex.)
Name
Description
Default
(Range)
Y4-43
(3D24)
Output Disconnect Inject
Current
Sets the level of DC injection current during output disconnect as a percentage of the drive rated
current.
30%
(5 - 50%)
◆
YA: Preset Setpoint
■
Setpoint Selection
Parameters
YA-01 [Setpoint 1]
to
YA-04 [Setpoint 4]
set the PID setpoint.
The priority over PID setpoint changes when the settings of MFDI functions
H1-xx = 3E and 3F [PID Setpoint
Selection 1 and 2]
change.
shows how the different MFDI functions (
H1-xx = 3E and 3F [PID Setpoint
Selection 1 and 2]
) have an effect on the PID setpoint value.
Table 5.67 Switching of MFDI and PID Setpoint Value
H1-xx = 3E
H1-xx = 3F
PID Setpoint Value
OFF
OFF
One of these values:
•
Frequency Reference (determined by
b1-01 [Frequency Reference Selection 1]
)
•
YA-01 [Setpoint 1]
(when
b1-01 = 0 [Keypad]
)
•
Analog Setpoint (when
H3-xx = C [MFAI Function Selection = PID Setpoint]
)
•
MEMOBUS setpoint
ON
OFF
YA-02 [Setpoint2]
OFF
ON
YA-03 [Setpoint3]
ON
ON
YA-04 [Setpoint4]
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...