YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
235
Table 5.32 Multi-step Speed Reference and MFDI Terminal Combinations
Related Parameters
Multi-Step Speed Reference 1
H1-xx = 3
Multi-Step Speed Reference 2
H1-xx = 4
Multi-Step Speed Reference 3
H1-xx = 5
Jog Reference
H1-xx = 6
Reference 1 (set in
b1-01
)
OFF
OFF
OFF
OFF
Reference 2 (
d1-02
or terminals
A1, A2)
ON
OFF
OFF
OFF
Reference 3 (
d1-03
or terminals
A1, A2)
OFF
ON
OFF
OFF
Reference 4 (
d1-04
)
ON
ON
OFF
OFF
Reference 5 (
d1-05
)
OFF
OFF
ON
OFF
Reference 6 (
d1-06
)
ON
OFF
ON
OFF
Reference 7 (
d1-07
)
OFF
ON
ON
OFF
Reference 8 (
d1-08
)
ON
ON
ON
OFF
Jog Reference (
d1-17
)
-
-
-
ON
*1
The Jog Frequency Reference (JOG command) overrides all other frequency references.
d1-01: Reference 1
d1-02: Reference 2
d1-03: Reference 3
d1-04: Reference 4
d1-05: Reference 5
d1-06: Reference 6
d1-07: Reference 7
d1-08: Reference 8
d1-17: Jog Reference
Figure 5.33 Time Chart for Multi-step Speed Reference/JOG Reference
■
d1-01: Reference 1
No.
(Hex.)
Name
Description
Default
(Range)
d1-01
(0280)
RUN
Reference 1
Sets the frequency reference in the units from
o1-03 [Frequency Display Unit Selection
.
0.00 Hz
(0.00 - 400.00 Hz)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...