5.1 A: Initialization Parameters
184
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Table 5.15 Parameters Saved as User Parameters with the Secondary Pump Preset
User Parameter No.
Parameter No. Saved
Name
A2-01
b1-03
Stopping Method Selection
A2-02
b1-04
Reverse Operation Selection
A2-03
b2-09
Pre-heat Current 2
A2-04
b5-01
PID Mode Setting
A2-05
b5-03
Integral Time (I)
A2-06
b5-08
PID Primary Delay Time Constant
A2-07
b5-09
PID Output Level Selection
A2-08
C1-01
Acceleration Time 1
A2-09
d2-03
Analog Frequency Ref Lower Limit
A2-10
H1-07
Terminal S7 Function Selection
A2-11
H3-01
Terminal A1 Signal Level Select
A2-12
H3-02
Terminal A1 Function Selection
A2-13
H3-10
Terminal A2 Function Selection
A2-14
L5-01
Number of Auto-Restart Attempts
A2-15
o1-24
Custom Monitor 1
A2-16
o1-25
Custom Monitor 2
A2-17
o1-26
Custom Monitor 3
A2-18
Y1-04
Sleep Wake-up Level
A2-19
Y1-05
Sleep Wake-up Level Delay Time
A2-20
Y1-08
Low Feedback Level
A2-21
Y1-09
Low Feedback Lvl Fault Dly Time
A2-22
Y2-01
Sleep Level Type
A2-23
Y2-02
Sleep Level
A2-24
Y2-03
Sleep Delay Time
A2-25
Y2-04
Sleep Activation Level
7 : Pump w/ PID Control
The drive automatically sets the parameters in
for a pump with PID control application.
Table 5.16 Optimal Settings for Pump with PID Control Applications
No.
Name
Optimal Value
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Disabled
b5-01
PID Mode Setting
1: Standard
b5-03
Integral Time (I)
15.0 s
b5-08
PID Primary Delay Time Constant
1.00 s
C1-01
Acceleration Time 1
20.0 s
d2-03
Analog Frequency Ref Lower Limit
20.0%
H3-10
Terminal A2 Function Selection
B: PID Feedback
L5-01
Number of Auto-Restart Attempts
10
L5-49
Fault Retry Speed Search Select
0: Disabled
S5-10
AUTO Key Memory at Power Down
1: Enabled w/ Memory
Y1-04
Sleep Wake-up Level
-5.00
Y1-05
Sleep Wake-up Level Delay Time
30 s
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...