YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
65
3.3
Main Circuit Wiring
This section gives information about the functions, specifications, and procedures necessary to safely and correctly
wire the main circuit in the drive.
NOTICE:
Damage to Equipment. The drive can fail if users frequently turn the drive ON and OFF with the MC on the power source
side to Run and Stop the drive. Incorrect operation can decrease the service life of the relay contacts and electrolytic capacitors. If
you frequently use the magnetic contactor on the power source side to Run and Stop the drive, it can cause drive failure.
Note:
Soldered wire connections can become loose over time and cause unsatisfactory drive performance.
◆
Motor and Main Circuit Connections
WARNING!
Electrical Shock Hazard. Do not connect terminals R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, -, +1, +2, +3, B1, or B2 to the
ground terminal. If you connect these terminals to earth ground, it can cause damage to the drive or serious injury or death.
A - DC bus terminal
B - Connect to the drive ground
terminal.
C - Ground the motor case.
D - Three-Phase Motor
E - Use R, S, T for input power supply.
F - Input Protection (Fuses or Circuit
Breakers)
Note:
The location of terminals are different for different drive models.
Figure 3.2 Wiring the Main Circuit and Motor
◆
Configuration of Main Circuit Terminal Block
Use
to find the correct main circuit terminal block figure for your drive.
Table 3.1 Configuration of Main Circuit Terminal Block
Model
Shape of Terminal
Figure
2004 - 2042, 4002 - 4023
European terminal
2056, 4031, 4038
European terminal
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...