120
YASKAWA
SIEPC71061737B GA800 Drive Technical Reference
3.12
Improve the Power Factor
◆
Connect an AC Reactor or a DC Link Choke
AC reactors and DC link chokes decrease surges in current and improve the power factor on the input side of the
drive.
Connect an AC reactor or a DC link choke the input side (primary side) in the these conditions:
•
To decrease harmonic current or improve the power factor of the power supply
•
When there is switching of phase advancing capacitor
•
With a large capacity power supply transformer (600 kVA or more).
Note:
•
You can use an AC reactor and DC link choke together.
•
When you connect a thyristor converter (for example, a DC drive) to the same power supply system, you should use an AC reactor,
regardless of the conditions of the power supply.
•
The main circuit terminal block for the drive, and the terminal blocks for the AC reactor and DC Link Choke come in different shapes. The
drive has a European-style terminal block, and the AC reactor and DC Link Choke have a circular terminal block. Correctly prepare the
ends of the wiring.
■
Connect an AC Reactor
Note:
When you connect an AC reactor to the output side (secondary side) of the driver, set
C6-02 = 1 [Carrier Frequency Selection = 2.0 kHz]
.
A - Power supply
B - MCCB
C - AC reactor
D - Drive
Figure 3.75 AC Reactor Connection Example
■
Connect a DC Link Choke
When you install a DC link choke, remove the jumper between ter1 and +2. If you will not use a DC link
choke, do not remove the jumper. Refer to
for an example of how to wire the DC link choke.
A - Power supply
B - MCCB
C - Drive
D - DC link choke
Figure 3.76 DC Link Choke Connection Example
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 20: ...i 3 Warranty Information 20 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 58: ...2 9 Installation Methods 58 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 268: ...5 6 Safe Disable Input 268 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 306: ...6 3 MEMOBUS Modbus Communications 306 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...
Page 426: ...8 7 Storage Guidelines 426 YASKAWA SIEPC71061737B GA800 Drive Technical Reference...