YASKAWA
TOEPYAIGA8002B GA800 Drive Programming
595
Parameters Automatically Set
Inertia Tuning
ASR Tuning
Deceleration Rate Tuning
KEB Tuning
C5-37 [Motor 2 Inertia]
x
x
-
-
C5-18 [Load Inertia Ratio]
x
x
-
-
C5-38 [Motor 2 Load Inertia
Ratio]
x
x
-
-
L2-06 [Kinetic Energy Backup
Decel Time]
-
-
-
L3-24 [Motor Accel Time @
Rated Torque]
x
x
-
-
L3-25 [Load Inertia Ratio]
x
x
-
x
n5-02 [Motor Inertia Acceleration
Time]
x
x
-
-
n5-03 [Feed Forward Control
Gain]
x
x
-
-
*1
The drive automatically sets
C1-08 [Deceleration Time 4]
only when
C1-11 [Accel/Decel Time Switchover Freq] ≠ 0
.
*2
When
L2-29 = 0 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 1]
, the drive will automatically adjust
C1-09 [Fast Stop
Time]
and will not adjust
L2-06 [Kinetic Energy Backup Decel Time]
. If the Fast Stop time must not change, do not do KEB Tuning.
*3
When
L2-29 = 1, 2, or 3 [Kinetic Energy Backup Method = Single Drive KEB Ride-Thru 2, System KEB Ride-Thru 1, or System KEB
Ride-Thru 2]
, the drive will automatically adjust
L2-06 [Kinetic Energy Backup Decel Time]
.
◆
Precautions before Auto-Tuning
Examine the topics in this section before you start Auto-Tuning.
■
Prepare for Basic Auto-Tuning
•
You must input data from the motor nameplate or motor test report to do Auto-Tuning. Make sure that this data is
available before Auto-Tuning the drive.
•
For best performance, make sure that the drive input supply voltage is equal to or more than the motor rated
voltage.
Note:
Better performance is possible when you use a motor with a rated voltage that is less than the input supply voltage (by 20 V for 200 V class
models or by 40 V for 400 V class models). This is very important when operating the motor at more than 90% of base speed, where high
torque precision is necessary. If the input power supply is equal to the motor rated voltage, the drive output voltage will not be sufficient, and
performance will decrease.
•
Push
on the keypad to cancel Auto-Tuning.
•
If a Safe Disable input signal is input to the drive during Auto-Tuning, Auto-Tuning measurements will not
complete successfully. If this occurs, cancel the Auto-Tuning, then do it again.
•
shows the status of input/output terminals during Auto-Tuning.
Table 3.14 Status of Input/Output Terminals during Auto-Tuning
Auto-Tuning Type
Mode
Multifunctional input
Multifunctional output
Induction Motor Auto-Tuning
Rotational
Rotational Auto-Tuning
Disabled
Functions the same as during usual
operation.
Stationary
Stationary Auto-Tuning 1
Disabled
Keeps the status at the start of
Auto-Tuning.
Line-to-Line Resistance
Disabled
Keeps the status at the start of
Auto-Tuning.
PM Motor Auto-Tuning
Rotational
Z-Pulse Offset (Pole Position)
Disabled
Keeps the status at the start of
Auto-Tuning.
PM Rotational Auto-Tuning
Disabled
Functions the same as during usual
operation.
Stationary
PM Motor Parameter Settings
Disabled
Disabled
PM Stationary Auto-Tuning
Disabled
Keeps the status at the start of
Auto-Tuning.
PM Stationary Auto-Tuning for
Stator Resistance
Disabled
Keeps the status at the start of
Auto-Tuning.