Figure 5.22 Configuration of Main Circuit Terminal Block (T477, T720)
◆
Main Circuit Terminal Functions
Refer to
for the functions of drive main circuit terminals.
Table 5.2 Main Circuit Terminal Functions
Terminal
Name
Function
Model
2004 - 2082
2110 - 2138
2169 - 2415
-
4002 - 4044
4060 - 4168
4208 - 4414
4477 - 4720
R/L1
Main circuit power supply input
To connect a commercial
power supply.
S/L2
T/L3
U/T1
Drive output
To connect a motor.
V/T2
W/T3
B1
Braking resistor connection
-
To connect a braking resistor
or braking resistor unit.
B2
+2
•
DC power supply input
(+1 and -)
•
DC reactor connection
(+1 and +2)
-
To connect peripheral
devices, for example:
•
DC power input
•
Braking Unit
•
DC Link Choke
Note:
Remove the jumper
between ter1
and +2 to connect a DC
link choke.
+1
DC power supply input (+1
and -)
•
DC power supply input (+1 and -)
•
Braking unit connection (+3 and -)
-
+3
-
•
200 V: D class grounding (ground to 100 Ω or less)
•
400 V: C class grounding (ground to 10 Ω or less)
To ground the drive.
Note:
Use terminals - and B1 to connect a CDBR-type control unit to drive models 2004 to 2138 and 4002 to 4168 that have built-in braking
transistors.
Summary of Contents for GA800 Series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 18: ...i 2 Using the Product Safely 18 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 72: ...1 7 Storage Guidelines 72 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 336: ...4 10 Installation Methods 336 YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting...
Page 565: ...YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance Troubleshooting 565...