TOEPYAIGA5002A GA500 Programming
This function fully stops a motor with a large inertia during deceleration and will not let the inertia continue to rotate
the motor.
Set this parameter to 0.00 to disable the function.
When a longer time is required to stop the motor, increase the value.
■
b2-08: Magnetic Flux Compensation Value
No.
(Hex.)
Name
Description
Default
(Range)
b2-08
(0190)
Magnetic Flux
Compensation Value
Sets how much current the drive injects when DC Injection Braking at Start starts (Initial Excitation)
as a percentage of
E2-03 [Motor No-Load Current]
.
0%
(0 - 1000%)
This parameter is effective when you start a high-capacity motor (a motor with a large secondary circuit time
constant). This function can quickly increase motor flux to make high starting torque (a process called initial
excitation).
The current level for DC Injection Braking at start changes linearly from the setting of
b2-08
to the setting of
b2-03
as
shown in
.
Figure 2.20 DC Current Level during DC Injection Braking at Start
Note:
•
If
b2-08 < 100%
, flux will develop very slowly.
•
When
b2-08 = 0%
, the DC current level will be the DC Injection current set in
b2-02 [DC Injection Braking Current]
.
•
If
b2-08
is set too high, DC Injection Braking at start can cause a large noise. Adjust
b2-08
to decrease the volume to the permitted level.
■
b2-12: Short Circuit Brake Time @ Start
No.
(Hex.)
Name
Description
Default
(Range)
b2-12
(01BA)
Short Circuit Brake Time @
Start
Sets the Short Circuit Braking time at start.
0.00 s
(0.00 - 25.50 s)
This function stops and restarts a coasting PM motor. The drive short circuits all the three motor phases to make
braking torque in the motor.
Set this parameter to 0.00 to disable the function.
Note:
•
Short circuit Braking will let external forces rotate the PM motor. Use DC Injection Braking to prevent motor rotation from external forces.
•
Motor speed and load conditions can make it necessary to install a dynamic braking option on the drive.
■
b2-13: Short Circuit Brake Time @ Stop
No.
(Hex.)
Name
Description
Default
(Range)
b2-13
(01BB)
Short Circuit Brake Time @
Stop
Sets the Short Circuit Braking time at stop.
A1-02 = 8: 0.00 s
Other than A1-02 = 8: 0.50 s
(0.00 - 25.50 s)
This function fully stops a PM motor with a large inertia during deceleration and will not let the inertia continue to
rotate the motor.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...