2.2 A: Initialization Parameters
YASKAWA
TOEPYAIGA5002A GA500 Programming
141
■
A1-03: Initialize Parameters
No.
(Hex.)
Name
Description
Default
(Range)
A1-03
(0103)
Initialize Parameters
Sets parameters to default values.
0
(0 - 3330)
Note:
•
After you initialize the drive, the drive automatically sets
A1-03 = 0
.
•
User Parameters can save the parameter values for your application and use these values as default values for drive initialization.
•
To use the 2 motor switchover function, first turn OFF the terminal to which
H1-xx = 16 [MFDI Function Selection = Motor 2 Selection]
is
set, then change the
A1-03
setting. An incorrect procedure will trigger
oPE08 [Parameter Selection Error]
.
0 : No Initialization
1110 : User Initialization
Sets parameters to the values set by the user as user settings. Set
o2-03 = 1 [User Parameter Default Value = Set
defaults]
to save the user settings.
You can save the parameter settings that were adjusted for the test run as user-set default values to the drive. When
you make changes to the parameter values after you save the settings as User Parameter Settings, the drive will set the
parameters to the User Parameter Setting value when you initialize with
A1-03 = 1110
.
Follow this procedure to save User Parameter setting values, and to do a User Initialization.
1. Set parameters correctly for the application.
2. Set
o2-03 = 1 [User Parameter Default Value = Set defaults]
.
This saves parameter settings for a User Initialization.
The drive will then automatically set
o2-03 = 0
.
3. Set
A1-03 = 1110
to reset to the saved parameter settings.
When you initialize the drive, the drive sets the parameter values to the User Parameter setting values.
2220 : 2-Wire Initialization
Sets MFDI terminal S1 to Forward Run and terminal S2 to Reverse Run, and resets all parameters to default settings.
3330 : 3-Wire Initialization
Sets MFDI terminal S1 to Run, terminal S2 to Stop, and terminal S5 to FWD/REV, and resets all parameters to
default settings.
The drive will not initialize the parameters in
when
A1-03 = 2220, 3330
.
Table 2.2 Parameters that are not Initialized Using a 2-Wire Sequence or a 3-Wire Sequence
No.
Name
A1-00
Language Selection
A1-02
Control Method Selection
A1-07
DriveWorksEZ Function Selection
A1-12
Bluetooth ID
E1-03
V/f Pattern Selection
E5-01
PM Motor Code Selection
E5-02
PM Motor Rated Power (kW)
E5-03
Motor Rated Current (FLA)
E5-04
PM Motor Pole Count
E5-05
PM Motor Resistance (ohms/phase)
E5-06
PM d-axis Inductance (mH/phase)
E5-07
PM q-axis Inductance (mH/phase)
E5-09
PM Back-EMF Vpeak (mV/(rad/s))
E5-24
PM Back-EMF L-L Vrms (mV/rpm)
E5-25
Polarity Estimation Timeout
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...