1.21 Defaults by Drive Model and Duty Rating ND/HD
116
YASKAWA
TOEPYAIGA5002A GA500 Programming
Name
Unit
Default
-
Drive Model
-
B010
B012
B018
C6-01
Normal / Heavy
Duty Selection
-
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
o2-04
Drive Model
(KVA) Selection
Hex.
34
35
37
E2-11
(E4-11, E5-02)
Motor Rated
Power
kW
1.5
2.2
2.2
3.0
3.7
5.5
E2-02
(E4-02)
Motor Rated Slip
Hz
2.6
2.9
2.9
2.7
2.73
1.5
E2-03
(E4-03)
Motor No-Load
Current
A
2.8
3
3
3.7
4.5
5.1
E2-05
(E4-05)
Motor Line-to-
Line Resistance
Ω
1.997
1.601
1.601
1.034
0.771
0.399
E2-06
(E4-06)
Motor Leakage
Inductance
%
18.5
18.4
18.4
19
19.6
18.2
E2-10
(E4-10)
Motor Iron Loss
W
53
77
77
91
112
172
E5-01
PM Motor Code
Selection
-
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
L2-02
Power Loss Ride
Through Time
s
0.3
0.3
0.5
0.5
1
1
L2-03
Minimum
Baseblock Time
s
0.4
0.5
0.5
0.5
0.6
0.7
L2-04
Powerloss V/f
Recovery Ramp
Time
s
0.3
0.3
0.3
0.3
0.3
0.3
L2-05
Undervoltage
Detection Lvl
(Uv1)
-
160
160
160
160
160
160
L3-02
Stall Prevent
Level during
Accel
%
150
120
150
120
150
120
L3-06
Stall Prevent
Level during Run
%
150
120
150
120
150
120
L3-24
Motor Accel Time
@ Rated Torque
s
0.166
0.145
0.145
0.145
0.154
0.168
L8-02
Overheat Alarm
Level
°C
105
105
110
110
115
115
L8-09
Output Ground
Fault Detection
-
0
0
0
0
0
0
n1-03
Hunting
Prevention Time
Constant
ms
10
10
10
10
10
10
n3-02
HSB Current
Limit Level
%
150
120
150
120
150
120
n5-02
Motor Inertia
Acceleration Time
s
0.166
0.145
0.145
0.145
0.154
0.168
*1
Parameters within parentheses are for motor 2.
Summary of Contents for GA500 series
Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 456: ...2 12 T Auto Tuning 456 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 488: ...3 8 Test Run Checklist 488 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 494: ...4 3 Remove and Reattach the Keypad 494 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 514: ...5 6 Connect the Drive to a PC 514 YASKAWA TOEPYAIGA5002A GA500 Programming...
Page 525: ...YASKAWA TOEPYAIGA5002A GA500 Programming 525...