Table 20.1 Applied Safety Standards and Unified Standards
Safety
Standards
Unified Standards
Functional
Safety
IEC/EN 61508:2010 (SIL3)
IEC 62061:2005/AMD2:2015 (SILCL3)
EN 62061:2005/A2:2015 (SILCL3)
IEC 61800-5-2:2016 (SIL3)
EN 61800-5-2:2017 (SIL3)
Machine
Safety
ISO/EN ISO 13849-1:2015 (Cat.3, PL e)
EMC
IEC 61000-6-7:2014
EN 61000-6-7:2015
IEC/EN 61326-3-1:2017
LVD
IEC 61800-5-1:2007/AMD1:2016
EN 61800-5-1:2007/A1:2017
Note:
SIL = Safety Integrity Level.
◆
Safe Disable Specifications
The Safe Disable input provides the stop function that complies with
“
Safe Torque Off
”
as
specified by IEC/EN61800-5-2. The Safe Disable input meets the requirements of ISO/
EN ISO 13849-1 and IEC/EN 61508. It also has a safety status monitor to detect safety
circuit errors.
When you install the drive as a component in a system, you must make sure that the
system complies with the applicable safety standards.
Refer to
for safety function specifications.
Table 20.2 Safe Disable Specifications
Item
Description
Input/Output
•
Input: 2
Safe Disable input (H1, H2)
Signal ON level: 18 Vdc to 28 Vdc
Signal OFF level: -4 Vdc to +4 Vdc
•
Output: 1
MFDO safety monitor output for external device
monitor (EDM)
Response time from when the input opens to when
the drive output stops
3 ms or less
Response time from when the H1 and H2 terminal
inputs open to when the EDM signal operates
30 ms or less