Wiring Main Circuit Terminals
2-
13
Main Circuit Terminal Functions
Main circuit terminal functions are summarized according to terminal symbols in
Table 2.4
. Wire the terminals
correctly for the desired purposes.
Table 2.4 Main Circuit Terminal Functions (200-240 V Class and 380-480 V Class)
Purpose
Terminal Symbol
Model: CIMR-G7U
208-240 Vac
480 Vac
Main circuit power input
R/L1, S/L2, T/L3
20P4 to 2110
40P4 to 4300
R1/L11, S1/L21, T1/L31
2018 to 2110
4018 to 4300
Drive outputs
U/T1, V/T2, W/T3
20P4 to 2110
40P4 to 4300
DC power input
1,
20P4 to 2110
40P4 to 4300
Braking Resistor Unit connec-
tion
B1, B2
20P4 to 27P5
40P4 to 4015
DC link choke connection
1, 2
20P4 to 2015
40P4 to 4015
Braking Transistor Unit con-
nection
3,
2018 to 2110
4018 to 4300
Ground
20P4 to 2110
40P4 to 4300