5
-58
Multi-function Analog Outputs: H4
User parameters for multi-function analog outputs are shown in the following table.
* In order to adjust the meter, 100% of the appropriate output is multiplied for the gain setting, the bias amount is added and then output.
See H4-02 when stopped in Quick, Advanced, or Verify mode. If 03 appears on the setting screen, then terminal FM is used.
See H4-04 when stopped in Quick, Advanced, or Verify mode. If 06 appears on the setting screen, then terminal AM is used.
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
MODBUS
Register
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
H4-01
Terminal
FM
Monitor
Selection
Selects the monitor output
(U1-xx) function for terminals
FM and FC. Refer to "U1-xx"
monitors for available settings.
Unavailable settings:
4, 10, 11, 12, 13, 14, 25, 28, 29,
30, 31, 34, 35, 39, 40, 41, 42,
47, 49, 50
1 to 48
2
No
A
A
A
A
A
41DH
Terminal
FM Sel
H4-02
Terminal
FM Gain
Setting
Sets terminal FM output level
when selected monitor is at
100%.*
0.00
to
2.50
1.00
Yes
Q
Q
Q
Q
Q
41EH
Terminal
FM Gain
H4-03
Terminal
FM Bias
Setting
Sets terminal FM output level
when selected monitor is at
0%.*
-10.0
to
10.0
0.0%
Yes
A
A
A
A
A
41FH
Terminal
FM Bias
H4-04
Terminal
AM
Monitor
Selection
Selects which monitor will be
the output on terminals AM and
FC. Same function choices as
H4-01.
1 to 48
3
No
A
A
A
A
A
420H
Terminal
AM Sel
H4-05
Terminal
AM Gain
Setting
Sets terminal AM output
voltage (in percent of 10Vdc)
when selected monitor is at
100% output.*
0.00
to
2.50
0.50
Yes
Q
Q
Q
Q
Q
421H
Terminal
AM Gain
H4-06
Terminal
AM Bias
Setting
Sets terminal AM output
voltage (in percent of 10Vdc)
when selected monitor is at 0%
output.*
-10.0
to
10.0
0.0%
Yes
A
A
A
A
A
422H
Terminal
AM Bias
H4-07
Terminal
FM Signal
Level
Selection
Selects the signal level of
terminal FM.
0: 0 to 10Vdc
1: -10 to +10Vdc
2: 4 to 20mA*
*Set the analog output jumper
CN15 in the proper position.
0 to 2
0
No
A
A
A
A
A
423H
AO Level
Select1
H4-08
Terminal
AM Signal
Level
Selection
Selects the signal level of
terminal AM.
0: 0 to 10Vdc
1: -10 to +10Vdc
2: 4 to 20mA*
*Set the analog output jumper
CN15 in the proper position.
0 to 2
0
No
A
A
A
A
A
424H
AO Level
Select 2