Quit New Gateway
Activate
Click “Test” to check the default configura-
tion and the ENC will query each inverter
in the daisy chain and display the connec-
tion with all units.
Make sure all inverters have unique
Modbus ID addresses. Select the appro-
prate Modbus Range for your system.
If the card has internet access and it is not
being blocked, it will display [OK]. Please
contact your network administrator, if
another message is received.
Once the “Test” is complete, the user
should be able to see all the inverters that
were found in the given range.
If the user is missing an inverter, make
sure it has a unique ID and it is within the
range. Once you find all the expected
inverters, please press “Save the Config”.
At this point the “Activate” button at the
top right corner should be highlighted.
DHCP
Inverter Baud Rate
Modbus Range
1 ~ 32
9600 N81
Test
Save the Config
Basic Ethernet RS485
---------------------------------------
Test:
1. Server Connection [ OK ]
2. Query Inverter 1...
Quit New Gateway Activate
DHCP
Upload Interval
Advanced Settings
1 Minutes
Test
Save the Config
Basic Ethernet RS485
Runtime: 25 Minutes
MQTT Connection: CONNECT
MQTT Server Host: yss.solectria.com 1883
Routing: LINK_ON
MAC: 00005E113C08
IP Address: 192.168.1.100
Mask: 255.255.255.0
Gateway: 192.168.1.1
DNS: 6.6.6.6