5.3 Types of Faults, Alarms, and Errors
YASKAWA ELECTRIC
TOEP C710687 02B FSDrive-MV1000 Instructions
145
T
ro
ubles
hoo
ting
5
Table 5.7 Fault Displays (2)
n
Minor Faults and Alarms
Refer to
for an overview of possible alarm codes. Conditions such as overvoltages can trip faults and alarms. It
is important to distinguish between faults and alarms to determine the proper corrective actions.
When the drive detects an alarm, the ALM indicator LED blinks and the alarm code display flashes. Most alarms trigger
a digital output programmed for alarm output (H2-
= 10). A fault (not an alarm) is present if the ALM LED lights
Refer to Faults (Drive Faults and Power Cell Faults) on page 144
for information of fault codes.
Table 5.8 Minor Fault and Alarm Displays
Digital Operator
Display
<1> The number of the Power Cell at which the fault has occurred is indicated by “nn”.
<2> Displayed as CPF00 or CPF20 when occurring at drive power up. When one of the faults occurs after successfully starting the drive, the display
will show CPF01 or CPF21.
Name
Page
Digital Operator
Display
Name
Page
oL1
Motor Overload
SEr
Too Many Speed Search Restarts
oL2
Drive Overload
SYNC
Commercial Synchronous Switching
Error
oL3
Overtorque Detection 1
oL4
Overtorque Detection 2
TME
Transformer Temperature Fault
oL5
Mechanical Weakening Detection 1
TME1
Transformer Temperature Fault 1
oL7
High Slip Braking oL
TME2
Transformer Temperature DI Fault
OOV
Output Overvoltage
TME3
Transformer Temperature Sensor
Disconnection
oPr
External Digital Operator Connection
Fault
UL3
Undertorque Detection 1
oS
Overspeed
(for Control Mode with PG)
UL4
Undertorque Detection 2
UL5
Mechanical Weakening Detection 2
PGo
PG Disconnect
(for Control Mode with PG)
Uv1
Undervoltage
Uv3
In-rush Prevention Circuit Error
PGoH
PG Hardware Fault
(detected when using a PG-X3 option)
VUB
Voltage Unbalance
Digital
Operator
Display
Name
Minor Fault
Output
(H2-
= 10)
Page
Digital
Operator
Display
Name
Minor Fault
Output
(H2-
= 10)
Page
BAT
Battery Voltage Low
Yes
oL1
Motor Overload
Yes
bb
Drive Baseblock (Voltage)
No
oL3
Overtorque 1
Yes
bUS
Option Communication Error
Yes
oL4
Overtorque 2
Yes
CALL
Serial Communication
Transmission Error
Yes
oL5
Mechanical Weakening
Detection 1
Yes
CE
MEMOBUS/Modbus
Communication Error
Yes
oS
Overspeed (for Control Mode
with PG)
Yes
CrST
Cannot Reset
No
PASS
MEMOBUS/Modbus Comm.
Test Mode Complete
No
dEv
Speed Deviation (for Control
Mode with PG)
Yes
PGo
PG Disconnect (for Control
Mode with PG)
Yes
dnE
Drive Disabled
Yes
PGoH
PG Hardware Fault (detected
when using a PG-X3 option)
Yes
EF
Forward/Reverse Run
Command Input Error
Yes
rUn
Motor Switch during Run
Yes
EF0
Option Card External Fault
Yes
SE
MEMOBUS/Modbus
Communication Test Mode
Error
Yes
EF1
to
EF16
External Fault (input
terminal)
Yes
FAn
Fan Fault
Yes
TMA1
Transformer Temperature
Fault
Yes
Summary of Contents for FSDrive-MV1000 Series
Page 8: ...8 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 106: ...3 9 Wiring Check 106 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 210: ...6 7 Spare Parts 210 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...
Page 222: ...B 1 European Standards 222 YASKAWA ELECTRIC TOEP C710687 02B FSDrive MV1000 Instructions...