Parameters A - 25
o2-10
Cumulative Cooling Fan
Operation Time Setting
Fan ON Time Set
Sets the initial value of the heatsink fan operation time.
0 to 65535
0 hours
Programming
o2-12
Fault Trace/Fault History Clear
Function
FLT Trace Init
Clears the fault memory contained in the U2 and U3
monitors.
0: Disabled (no effect)
1: Enabled - resets U2 and U3 monitors, and returns
o2-12 to zero
0 or 1
0
Programming
o2-14
kWh User Monitor (U1-29)
Initialization
kWh MonitorClear
Used to reset the kilowatt Hour monitor to zero
0: Disabled (no change)
1: Clear all - Resets U1-29 to zero and returns o2-14 to
zero.
0 or 1
0
Programming
o2-15
Hand Key Function Selection
Oper Hand Key
Enables or disables the "Hand" key on the digital
operator.
0: Disabled
1: Enabled
0 or 1
1
Programming
COPY Function
o3-01
Copy Function Selection
Copy Function Sel
This parameter controls the copying of parameters to
and from the digital operator.
0: COPY SELECT (no function)
1: INV -> OP READ - All parameters are copied from
the drive to the digital operator.
2: OP -> INV WRITE - All parameters are copied from
the digital operator into the drive.
3: OP<-->INV VERIFY - Parameter settings in the drive
are compared to those in the digital operator.
NOTE: When using the copy function, the drive model
number and software number (U1-14) must match or an
error will occur.
0 to 3
0
Programming
o3-02
Read Allowed Selection
Read Allowable
Enables and disables all digital operator copy functions.
0: Disabled - No digital operator copy functions are
allowed
1: Enabled - Copying allowed
0 to 1
0
Programming
Auto-Tuning
T1-02
Motor Rated Power
Mtr Rated Power
Sets the motor rated power in kW.
NOTE: T1-02 should be left at the Drive default (the last
3 digits of the Drive model number).
0.00 to
650.00
kVA
Dependent
Auto-Tuning
T1-04
Motor Rated Current
Rated Current
Sets the motor rated current.
(Used only during an auto-tune).
kVA
Dependent
kVA
Dependent
Auto-Tuning
Table A.2 Monitor List
Parameter
No.
Parameter Name
LCD Digital Operator Display
Description
Monitor
U1-01
Frequency Reference
Frequency Ref
Frequency reference (speed command) monitor when in auto
mode, frequency reference (speed command) setting location
when in hand mode. Units changeable via o1-03.
U1-02
Output Frequency
Output Freq
Output frequency (speed) monitor. Units changeable via
o1-03.
U1-03
Output Current
Output Current
Output current monitor
U1-06
Output Voltage
Output Voltage
Displays Drive output voltage
Table A.1 Parameter List (Continued
)
Parameter
No.
Parameter Name
LCD Digital Operator Display
Description
Setting
Range
Factory
Setting
Menu
Location
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com