Start Up and Operation 4 - 7
Table 1 is also used to document parameters that have been factory set to typical values for fan and pump
applications. These parameters [
b1-07
,
b1-08
,
b8-01
,
L4-05
,
L5-01
,
L5-03
,
o1-02
,
o2-03
and
o3-02
] may be
changed to meet the needs of the specific application.
4. From the
ADV/PRGM
menu, press
DATA/ENTER
, go to parameter
E1-01
and enter the nominal input voltage that
the Drive will receive in this specific application. The overall voltage classification of the Drive cannot be changed by
this parameter. However, the input voltage should be adjusted within the range available for the given voltage “class”
of the Drive to match the input voltage level normally found on the jobsite. For example, 480 VAC class Drives may
be employed on nominal three phase voltage distribution systems of: 380, 400, 415, 440, 460 or 480 VAC. The factory
default values may need to be changed to meet the needs of the application distribution voltage.
5. From parameter
E1-01
, use the ESC,
¿
and
DATA/ENTER
keys as necessary, to go to parameter
E2-01
and enter
the Motor Rated Current. Set this parameter to the motor rated Full Load Amps (FLA) shown on the motor nameplate.
This is essential for proper Drive operation and motor overload protection. [
Note:
Do not include the “service factor”
amps.]
6. Press the
MENU
key to return to the
DRIVE
menu and the same operational status LED configuration described in
step 2 above. The alpha/numeric display will now be the speed command frequency.
To start the motor in Drive mode, press the
HAND
key. The
DRIVE Run
LEDs (red and green) and the
HAND
LED
(amber) will light and the Drive output will ramp up to “6 HZ.” Verify that motor rotation is correct.
If the direction of motor rotation is wrong, press the
OFF
key and turn the Power
OFF
! Wait for the red
CHARGE
LED (near the Drive power terminals) to go out. When it does, swap the wires for
T1
&
T2
on the output terminals
of the motor Overload Relay. Tighten the terminal lugs, reapply the power, press the
HAND
key and re-check the
rotation direction.
7. With correct motor rotation, press the
MENU
key, if necessary, to return to the
DRIVE
menu. Press
DATA/ENTER
(as needed to get “F” flashing) then using the
¿
and
À
keys, manually run the Drive throughout its entire speed
range, while observing operation. If excessive vibration of the driven load is noted at specific frequencies (speeds), the
Jump Frequency function may be used to eliminate this vibration, by programming
d3-01
through
d3-04
. Press the
OFF
key.
8. Determine whether the remote speed command is a 0-10 VDC or a 4-20 mA signal. The positive side of the signal
should be connected to terminal
TB3-3
of the E7N terminal strip. The “common” of the remote speed command
signal should be connected to terminal
TB3-1
of the E7N. See the connection diagram on page 1 of the E7N Bypass
unit schematic E7N-00 (or Chapter 5 in this manual). [
Note:
The factory default is 4-20 mA, to change to 0 to 10 VDC
adjust parameter
H3-08
to “0: 0-10VDC” and move E7N DIP switch
S1-2
, on the terminal PCB to the OFF
position (toward the unit rear).]
9. For the Auto mode, request a run command and speed command signal from the building automation system to
confirm remote (auto) operation.
10. Press the
AUTO
key, the
DRIVE Run
LEDs (red and green), the
AUTO
LED (green) and
AUTO Run
LED (green)
will light and the Drive output will ramp up to the Auto mode speed command. Observe if the remote speed command
can achieve the minimum and maximum speeds desired. If not, perform the following: - See Chapter 5.
For 0-10 VDC input at Terminal
TB3-3
1. With no input, adjust the Bias (
H3-11
setting) until an output of “0.0 Hz” is obtained.
2. With full scale input, adjust the Gain (
H3-10
setting) until an output of “60.0 Hz” (or other desired maximum
frequency) is obtained.
For 4-20 mA input at Terminal
TB3-3
1. With 4 mA input, adjust Bias (
H3-11
setting) until an output of “0.0 Hz” is obtained.
2. With 20 mA input, adjust Gain (
H3-10
setting) until an output of “60.0 Hz” (or other desired maximum
frequency) is obtained.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com