90
YASKAWA
TOEPC71061723A YASKAWA AC Drive CR700 Quick Start Guide
Figure 15.3 Wiring Example for DC Power Supply Input
Note:
•
Install a fuse for each drive when operating more than one drive. If one fuse blows, replace all fuses.
•
Install the external filter (system) to comply with the EMC Directive.
•
Do not ground the main circuit bus.
Refer to
and
for the recommended fuses.
Three-Phase 200 V Class
Table 15.6 Recommended Fuse (Three-Phase 200 V Class)
Drive Model
Fuse
Manufacturer: Bussmann
Model
Qty
2003
FWH-45B
2
2005
FWH-45B
2
2008
FWH-45B
2
2011
FWH-100B
2
2014
FWH-100B
2
2018
FWH-100B
2
2025
FWH-125B
2
2033
FWH-150B
2
2047
FWH-200B
2
2060
FWH-250A
2
2075
FWH-250A
FWH-300A
2
2088
FWH-250A
FWH-275A
2
2115
FWH-300A
FWH-350A
2
2145
FWH-350A
FWH-450A
2
2180
FWH-450A
FWH-600A
2
2215
FWH-600A
FWH-700A
2
2283
FWH-800A
FWH-1000B
2
2346
FWH-1000B
2
2415
FWH-1000B
2
*1
Yaskawa recommends a fuse with a large rated current for applications with repeated loads.