EtherNet/IP 3-20
* The type of physical outputs and their terminal designations for outputs controlled by bits 0 and 1 differ according to the drive. Refer to the
appropriate drive user, programming and/or technical manual for details on digital outputs.
Class 65h - Yaskawa Status Object
Attributes
* Parameter o2-04 for kVA model - Scaling is 0.01A for kVA models 00h ~ 06h and 20h ~ 26h
Yaskawa Command Object – Class 64h, Instance 1, Attribute 8 – Digital Output
Bit
Definition
0
PHC 1 – Multi-function Digital Output 1 – Parameter H2-01 setting*
1
PHC 2 – Multi-function Digital Output 2 – Parameter H2-02 setting*
2
Reserved
3
Reserved
4
Reserved
5
Reserved
6
Fault Contact Enable
7
Fault Contact – Bit 6 must be set to 1 in order to enable the function of bit 7
Service Code No. (hex)
Service Name
0E
Get Attribute Single
10
Set Attribute Single
Instance ID
Attribute
Description
Get
Set
Size
Default Value
0
1
Object software Revision
X
Word
1
1
1
Drive Status
X
Word
0
2
Speed Feedback (o1-03 scaled)
X
Word
0
3
Torque Reference (0.1%)
X
Word
0
4
Speed Detection PG Count
X
Word
0
5
Speed Reference (o1-03 scaled)
X
Word
0
6
Output Frequency (o1-03 scaled)
X
Word
0
7
Output Current*
X
Word
0
8
Analog Input Channel 2
X
Word
0
9
DC bus Voltage (1V)
X
Word
0
10 (0Ah)
Fault Code 1
X
Word
0
11 (0Bh)
Fault Code 2
X
Word
0
12 (0Ch)
Fault Code 3
X
Word
0
13 (0Dh)
Analog Input Channel 3 (F7U/G7U only)
X
Word
0
14 (0Eh)
Digital Input 2
X
Word
0
15 (0Fh)
Analog Input Channel 1
X
Word
0
16 (10h)
Channel 2 PG Counter
X
Word
0
Summary of Contents for CM092