Three-Phase 400 V Class
Model
Terminal
Recomm.
Gauge
mm
2
Applicable
Gauge
mm
2
Wire
Stripping
Length
mm
Terminal
Screw
Size and
Shape
Tightening
Torque
N
∙
m (lbf
∙
in)
4001
R/L1, S/L2, T/L3
2.5
2.5 - 4
8
M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3
2.5
2.5 - 4
8
M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2
2.5
2.5 - 4
8
M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2
2.5
2.5 - 4
8
M3
0.5 - 0.6
(4.4 - 5.3)
2.5
2.5 - 6
-
M4
1.2 - 1.5
(10.6 - 13.3)
4002
R/L1, S/L2, T/L3
2.5
2.5 - 4
8
M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3
2.5
2.5 - 4
8
M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2
2.5
2.5 - 4
8
M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2
2.5
2.5 - 4
8
M3
0.5 - 0.6
(4.4 - 5.3)
2.5
2.5 - 6
-
M4
1.2 - 1.5
(10.6 - 13.3)
4004
R/L1, S/L2, T/L3
2.5
2.5 - 4
8
M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3
2.5
2.5 - 4
8
M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2
2.5
2.5 - 4
8
M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2
2.5
2.5 - 4
8
M3
0.5 - 0.6
(4.4 - 5.3)
4
2.5 - 6
-
M4
1.2 - 1.5