162
YASKAWA
TOEPC7106170YB YASKAWA AC Drive GA500 Installation & Primary Operation
Code
Name
Causes
Possible Solutions
oPE11
Carrier Frequency
Setting Error
These parameters are set at the
same time:
•
C6-05 > 6 [Carrier Freq
Proportional Gain > 6]
•
C6-04 > C6-03 [Carrier
Frequency Lower Limit >
Carrier Frequency Upper
Limit]
Note:
When
C6-05 < 7
,
C6-04
becomes disabled. The drive
sets the carrier frequency to
the value set to
C6-03
.
C6-02 to C6-05
settings are not
in the applicable setting range.
Set
C6-02 to C6-05
correctly.
oPE13
Pulse Monitor
Selection Error
H6-06 = 101, 102, 105, or 116
[Terminal MP Monitor
Selection = Frequency
Reference, Output Frequency,
Motor Speed, Output Frequency
after Soft Starter]
has not been
set when
H6-07 = 0 [Terminal
MP Frequency Scaling = 0 Hz]
.
Set
H6-06
correctly.
oPE16
Energy Saving
Constants Error
The Energy Saving parameters
are not set in the applicable
setting range.
Make sure that
E5-xx
is set correctly as
specified by the motor nameplate data.