![YASKAWA CIMR-ZU Series Programming Manual Download Page 319](http://html1.mh-extra.com/html/yaskawa/cimr-zu-series/cimr-zu-series_programming-manual_907183319.webp)
Register No.
Contents
002CH
Drive Status 2
bit 0
During Run
bit 1
Zero Speed
bit 2
Speed Agree
bit 3
User Speed Agree
bit 4
Frequency Detection 1
bit 5
Frequency Detection 2
bit 6
Drive Ready
bit 7
During Undervoltage
bit 8
During Baseblock
bit 9
Frequency Reference from Operator Keypad
bit A
Run Command from Operator Keypad
bit B
Over/Undertorque 1
bit C
Frequency Reference Loss
bit D
During Fault Restart
bit E
Fault
bit F
Communication Timeout
002DH
Output Terminal Status
bit 0
Multi-Function Contact Output 1 (terminal M1-M2)
bit 1
Multi-Function Contact Output 2 (terminal M3-M4)
bit 2
Multi-Function Contact Output 3 (terminal M5-M6)
bit 3 to 6
Reserved
bit 7
Fault Contact Output (terminal MA/MB-MC)
bit 8 to F
Reserved
002EH
Reserved
002FH
Frequency Reference Bias (from Up/Down 2 Function), 0.1% units
0030H
Reserved
0031H
DC Bus Voltage, 1 Vdc units
0032H, 0033H
Reserved
0034H
Product Code 1 [ASCII], Product Type (Z0 for Z1000)
0035H
Product Code 2 [ASCII], Region Code
0036H, 0037H
Reserved
0038H
PI Feedback, 0.1% units, unsigned, 100% / max. output frequency
0039H
PI Input, 0.1% units, signed, 100% / max. output frequency
003AH
PI Output, 0.1% units, signed, 100% / max. output frequency
003BH, 003CH
Reserved
003DH
bit 0
CRC Error
bit 1
Data Length Error
bit 2
Reserved
bit 3
Parity Error
bit 4
Overrun Error
bit 5
Framing Error
bit 6
Timeout
bit 7 to F
Reserved
003EH
Output Frequency
r/min
003FH
0.01% units
0040H to 004AH
Used for various monitors U1-
oo
.
Refer to U: Monitors on page 232
for parameter details.
E.9 MEMOBUS/Modbus Data Table
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual