C6-03
C6-04
E1-04
x C6-05
Output Frequency
Output
Frequency
Max Output Frequency
Carrier Frequency
Figure 1.22 Carrier Frequency Changes Relative to Output Frequency
Note:
When C6-05 is set lower than 7, C6-04 is disabled and the carrier frequency will be fixed to the value set in C6-03.
u
Rated Current Depending on Carrier Frequency
The tables below show the drive output current depending on the carrier frequency settings.
The 2 kHz values shown in
are equal to the drive rated current shown on the drive nameplate. Increasing the carrier
frequency above 2 kHz will reduce the rated output current of the drive.
Table 1.13 Three-Phase 600 V Class Carrier Frequency and Current Derating
Three-Phase 600 V Class
Drive Model
Rated Current [A]
2 kHz
8 kHz
10 kHz
15 kHz
5A0003
2.7
2.2
2.0
1.3
5A0004
3.9
3.4
3.1
2.1
5A0006
6.1
4.9
4.3
2.9
5A0009
9
7.5
6.6
4.5
5A0011
11
9.3
8.2
5.6
5A0017
17
13.3
11.8
–
5A0022
22
17.0
15.1
–
5A0027
27
22.0
19.5
–
5A0032
32
27.3
24.4
–
Three-Phase 600 V Class
Drive Model
Rated Current [A]
2 kHz
5 kHz
8 kHz
10 kHz
5A0041
41.0
39.7
33.5
29.4
5A0052
52.0
50.3
42.5
37.3
5A0062
62.0
61.3
49.7
41.9
5A0077
77.0
76.2
61.7
52.0
5A0099
99.0
80.0
55.1
–
Three-Phase 600 V Class
Drive Model
Rated Current [A]
2 kHz
3 kHz
5A0125
125.0
93.0
5A0145
145.0
108.0
5A0192
192.0
148.0
5A0242
242.0
187.0
1.3 C: Tuning
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
55
1
Parameter Details