D.2 Communication Specifications
Metasys N2 specifications appear in the following table:
Item
Specifications
Interface
RS-485
Communication Parameters
Communication Speed: 9600 bps
Data Length: 8-bit (fixed)
Parity: None
Stop Bit: 1-bit (fixed)
Protocol
Metasys N2
Max Number of Drives
255 per N2 Network Segment
D.2 Communication Specifications
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual