A.2
Single/Three-Phase 200 V Class Drive
Table A.2 Power Ratings
Item
Specification
Three-Phase: CIMR-J
o
2A
0001 0002 0004 0006 0008 0010 0012 0018 0020
Single-Phase: CIMR-J
o
0001 0002 0003 0006
-
0010
-
-
-
Maximum Motor Size Allowed
(kW)
ND Rating
0.2
0.4
0.75
1.1
1.5
2.2
3.0
3.7
5.5
HD Rating
0.1
0.2
0.4
0.75
1.1
1.5
2.2
3.0
3.7
Input
Input
Three-
Phase
ND Rating
1.1
1.9
3.9
7.3
8.8
10.8 13.9
18.5
24.0
HD Rating
0.7
1.5
2.9
5.8
7.0
7.5
11.0
15.6
18.9
Single-
Phase
ND Rating
2.0
3.6
7.3
13.8
–
20.2
-
–
–
HD Rating
1.4
2.8
5.5
11.0
–
14.1
-
–
-
Output
Rated Output Capacity
(kVA)
ND Rating
0.5
0.7
1.3
2.3
3.0
3.7
4.6
6.7
7.5
HD Rating
0.3
0.6
1.1
1.9
2.6
3.0
4.2
5.3
6.7
Output Current (A)
ND Rating
1.2
1.9
3.5
(3.3)
6.0
8.0
9.6
12.0
17.5
19.6
HD Rating
0.8
6.9
11.0
Overload Tolerance
ND Rating: 120% of rated output current for 1 minute
HD Rating: 150% of rated output current for 1 minute
(Derating may be required for applications that start and stop
frequently)
Carrier Frequency
2 kHz (user-set, 2 to 15 kHz)
Max Output Voltage (V)
Three-phase 200 to 240 V (proportional to input voltage)
Max Output Frequency (Hz)
400 Hz (user-adjustable)
Power
Supply
Rated Voltage
Rated Frequency
Three-phase power: Three-phase 200 to 240 V 50/60 Hz
Single-phase power: 200 to 240 V 50/60 Hz
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Harmonic Corrective
Actions
DC Reactor
Optional
<1>
Drives with a single-phase power supply input output three-phase power, and cannot run a single-phase motor.
<2>
The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps
should be equal to or greater than the motor rated current.
<3>
Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and
power supply impedance.
<4>
Rated motor capacity is calculated with a rated output voltage of 220 V.
<5>
Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<6>
Carrier frequency is set to 10 kHz. Current derating is required in order to raise the carrier frequency.
<7>
Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.
Note:
Differences between Heavy Duty (HD) ratings and Normal Duty (ND) ratings for the drive include rated
input and output current, overload capacity, carrier frequency and current limit. Set parameter C6-01 to “0”
for HD or “1” for ND (default).
A.2 Single/Three-Phase 200 V Class Drive
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
189
A
Specifications
2/6/2008-14:44