Individual Functions
6-
101
Multi-Function Contact Inputs (H1-01 to H1-10)
Multi-Function Analog Input (H3-05, H3-09)
Parameter
Number
Name
Description
Output Signal Level During
Multi-Function Analog
Output
Min.
Unit
Control Methods
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
U1-24
PI Feedback
Value
Feedback signal level when PID
control is used.
10V: Maximum Frequency
(possible for -10V thru +10V)
0.01
%
A
A
A
A
A
PID
Feedback
U1-36
PID Input
Input error to the PID regulator
(PID Setpoint - PID Feedback).
10V: Maximum Frequency
(possible for -10V thru +10V)
0.01
%
A
A
A
A
A
PID Input
U1-37
PID Output
Output of the PID regulator as a
percentage of maximum
frequency (E1-04).
10V: Maximum Frequency
(possible for -10V thru +10V)
0.01
%
A
A
A
A
A
PID Output
U1-38
PID Setpoint Setpoint of the PID regulator
(PID ref PID bias).
10V: Maximum Frequency
0.01
%
A
A
A
A
A
PID Setpoint
Setting
Value
Function
Control Methods
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
19
PID control disable (ON: PID control disabled)
Yes
Yes
Yes
Yes
Yes
30
PID control integral reset (reset when reset command is input or when stopped during
PID control)
Yes
Yes
Yes
Yes
Yes
31
PID control integral hold (ON: Hold)
Yes
Yes
Yes
Yes
Yes
34
PID soft starter
Yes
Yes
Yes
Yes
Yes
35
PID input characteristics switch
Yes
Yes
Yes
Yes
Yes
Setting
Value
Function
Contents (100%)
Control Methods
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
B
PID feedback
Maximum output frequency
Yes
Yes
Yes
Yes
Yes
C
PID target value
Maximum output frequency
Yes
Yes
Yes
Yes
Yes