User Parameters Settable in Quick Programming Mode
The minimum user parameters required for Drive operation can be monitored and set in quick programming
mode. The user parameters displayed in quick programming mode are listed in the following table. These, and
all other user parameters, are also displayed in advanced programming mode.
Refer to the overview of modes on page 3-5 for an overview of quick programming mode.
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
MODBUS
Register
Display
V/f
V/f
with
PG
Open
-loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
A1-02
Control
Method
Selection
Selects the Control Method of the Drive.
0: V/F control without PG
1: V/F control with PG
2: Open Loop Vector
3: Flux Vector (Closed Loop Vector)
4: Vector 2 wo/PG
Note: Does not return to factory
setting when drive is initialized.
0 to 4
2
No
Q
Q
Q
Q
Q
102H
Control
Method
b1-01
Frequency
Reference
Selection
Selects the frequency reference input
source.
0: Operator - Digital preset speed U1-
01 or d1-01 to d1-17.
1: Terminals - Analog input terminal
A1 (or terminal A2 based on
parameter H3-09).
2: Serial Com - Modbus RS-422/485
terminals R+, R-, S+, and S-.
3: Option PCB - Option board
connected on 2CN.
4: Pulse Input (Terminal RP)
0 to 4
1
No
Q
Q
Q
Q
Q
180H
Reference
Source
b1-02
Run
Command
Selection
Selects the run command input source.
0: Operator - RUN and STOP keys on
Digital Operator.
1: Terminals - Contact closure on
terminals S1 or S2.
2: Serial Com - Modbus RS-422/485
terminals R+, R-, S+, and S-.
3: Option PCB - Option board
connected on 2CN.
0 to 3
1
No
Q
Q
Q
Q
Q
181H
Run
Source
b1-03
Stopping
Method
Selection
Selects the stopping method when the
run command is removed.
0: Ramp to Stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast with Timer (A new run
command is ignored if received
before the timer expires).
0 to 3
*13
0
No
Q
Q
Q
Q
Q
182H
Stopping
Method
C1-01
Acceleration
Time 1
Sets the time to accelerate from zero to
maximum frequency.
0.0
to
6000.0
*1
10.0 s
Yes
Q
Q
Q
Q
Q
200H
Accel
Time 1
C1-02
Deceleration
Time 1
Sets the time to decelerate from maxi-
mum frequency to zero.
Yes
Q
Q
Q
Q
Q
201H
Decel
Time 1