Yaskawa Solectria Solar
DOCR-071070
Page 18 of 30
INFO
✔
The De-Combiner comes from the factory with the XGI 1500 inverters’ Equipment Ground Conductors
pre-wired to the ground lugs. Torque each EGC per the specifications below.
Table 3-6: Equipment Grounding Lug
EQUIPMENT GROUND LUG (3X)
CU OR AL CONDUCTORS
MIN: 14 AWG
MAX: 2/0 AWG
90C TEMPERATURE RATED
TORQUE TO 20 IN-LB
STEP 5: Final Steps
CAUTION
Verify the proper polarity of each conductor. Polarity reversal can lead to dangerous conditions
capable of harming personnel and equipment.
INFO
✔
Check the De-Combiner for tools and debris; ensure that the unit is clean and orderly.
1.
Verify that all connections meet the requirements of this User’s Manual.
2.
Secure the De-Combiner cover, ensuring that all fasteners are in place.
3.
Consult the startup and commissioning procedures for the system before energizing.