6 Related Parameters
6
Related Parameters
The parameters outlined in the following sections are used to set up the unit for operation
with the option. Set parameters as needed. Parameter setting methods can be found in the
drive unit Instruction Manual.
◆
Parameter F5-09
Set parameter F5-09 to select the option output mode.
shows the changes in the output terminal contents according to the output mode set
in F5-09.
Table 5 F5-09 and Output Mode
Table 6 Binary Coded Output (F5-09 = 1)
Terminal
Block
Terminal
F5-09 = 0
Individual Output
(Default when Installed to
Drive)
F5-09 = 1
Binary Code Output
F5-09 = 2
Multi-Function Output
(Default when Installed
to D1000)
TB1
M1-M2
Zero speed
During run
Determined by F5-07
M3-M4
Speed agree
Alarm (excluding bb)
Determined by F5-08
TB2
P1-PC
oC, GF (Overcurrent)
Binary code output
(Refer to
)
Determined by F5-01
P2-PC
ov (Overvoltage)
Determined by F5-02
P3-PC
oH2 (Unit overheat)
or oL2 (overload)
Determined by F5-03
P4-PC
Not used
Determined by F5-04
P5-PC
oS (Overspeed)
Zero speed
Determined by F5-05
P6-PC
oH, oH1 (Unit overheat)
or oL1 (Overload)
Speed agree
Determined by F5-06
Coded Output
Description
TB2
P1-PC
P2-PC
P3-PC
P4-PC
0
Normal operation (no fault)
0
0
0
0
1
oC, GF (Overcurrent)
1
0
0
0
2
ov (Overvoltage)
0
1
0
0
3
oL2 (Unit overload)
1
1
0
0
4
oH, oH1 (Unit overheat)
0
0
1
0
5
oS (Overspeed)
1
0
1
0
6
Not used
0
1
1
0
7
rr, rH (Braking resistor overheat)
1
1
1
0
8
EF1 to EF12 (External fault)
0
0
0
1