![background image](http://html.mh-extra.com/html/yamato/cf800/cf800_instruction-manual_905426011.webp)
8
Before Using this unit
Requirements for Installation
10. Secure sufficient ventilation for the unit.
Do not operate the unit when its side panels and vent holes are blocked.
Internal temperature of the unit will rise degrading the performance and an accident, a
malfunction or a fire may result.
11. Do not operate the unit at such a place that may subject to splash.
Do not operate the unit at such a place that may subject to splash. Liquid entering the inside may
cause an accident, a malfunction, an electrical shock or a fire.
12. Do not use liquid other than water and antifreezing liquid (Nybrine
®
, ethylene glycol)
Pour distilled water or tap water into the water tank. Water of poor quality may cause fur or
scale to accumulate on the heater pump, which may result in deteriorated performance or
malfunction (e.g. well water, etc.).
When you use circulation liquid have a high degree of inflammability such as ethanol, please
perform sufficient ventilation and do not bring close what becomes fire and a source of
ignition by any means.
A circulating liquid with high specific gravity or highly viscosity places overburden on the
circulating pump and damages the unit (e.g. Fluorinert, Galden, etc.).
A corrosive liquid or a liquid that produces corrosive substances when heated may cause
malfunction (e.g. Fluorinate). Also when you mix an antiseptic with an antifreeze solution,
please choose a thing without corrosiveness.(Main parts
:
Stainless steel plate, Copper,
Nickel plate, Silicon rubber)
Do not use any liquid whose vapor is toxic or hazardous because it may result in an accident
(methyl alcohol, etc.).