Separate transformer

Operation check

Make sure that only the green LED starts blinking within
one minute of the power turning ON.
(During normal operation, only the green LED blinks.)

Maintenance

Periodic Calibration

We recommend calibrating the transmitter once every
year.    However, determine the calibration period
according to the amount of dust or dirt in the test gas.

Calibration

1. Initial Calibration

The CO

2

 concentration transmitter is inspected and

adjusted before it is shipped from the factory.    So, 

it

does not need to be adjusted at the installation
site.

2. Periodic Inspection

We recommend inspecting inside the case (circuit
boards, etc.) of the CO

2

 concentration transmitter as

test gas enters the case.

Calibration Method

The separate CO

2

 Service Bag (procurement item No.:

83104511-001) is needed for calibrating the transmitter.

1. Remove the cover from the CO

2

 concentration

transmitter.

2. Insert the inlet (tube tip) of the CO

2

 Service Bag into the

CO

2

 concentration zero gas inlet as shown in the figure

at the bottom right.

3. Turn the CO

2

 service bag ON to start supply of CO

2

concentration zero gas to the CO

2

 concentration

transmitter.

4. With the zero gas still supplied, wait for the CO

2

concentration to stabilize.    (Generally, this takes about
five minutes.)

5. When CO

2

 concentration has stabilized, calibrate the

CO

2

 concentration transmitter. (zero adjustment

completion method using buttons)
1) Simultaneously hold down the (+) and (-) buttons on

the circuit board.    Hold these buttons down for
about five seconds until the yellow and red LEDs

light.  This sets the CO

2

 concentration transmitter to

the service mode.    (In this state, the CO

2

concentration and "OP1" are displayed alternately
on the LCD panel.)

2) Press the (+) once. The LCD panel display changes

to indicate the CO

2

 concentration and "OP2".    This

indicates that the calibration menu is entered.    If
"OP2" is not displayed, press the (+) key again until
"OP2" is displayed.

3) Hold down the (-) button for about three seconds

until all LEDs (green, yellow, red) light.    This starts
calibration.    All LEDs light when calibration begins
and go out when calibration ends.    When all LEDs
go out, this indicates that the CO

2

 concentration

transmitter has returned to the standard
measurement mode.

IMPORTANT:

Press the (-) button at only OP2.

  Do not

press this button at other menu items.    (If you

press the (-) button at different menu item, the

functions of the CO

2

 concentration transmitter

are sometimes adversely affected.    If you have

executed a different menu item, contact a

Yamatake service engineer.)

6. Tighten the cover of the CO

2

 concentration transmitter.

(During this operation, do not mistake the top and
bottom of the cover.    (If you do so, the arrow will face
the opposite direction.))

To return to the user mode from the service mode
without calibrating the CO

2

 concentration transmitter,

repeatedly press the (+) button to advance the service
mode one menu item at a time.    Advance the mode
"OP1" 

 "OP2" 

 "OP3" 

 "OP4" 

 "OP5" 

"OP6" 

  and press the (+) button again to return to the

user mode.

Y

24 VAC

Multi-loop

controller

Y

24 VAC

GOOD

No common loop formed